Part #: 265888

Universal Control Card

7

Innovators in Clean Air Technology | www.envirco.com

A d v a n c e d Te c h n i c a l M a n u a l

COMMUNICATION SPECIFICATIONS

Overview:

MODBUS RTU protocol over RS485 (serial)

9600 baud rate, word length is 8, parity is none(n), stop bits=1

255 unique address values selectable by DIP switch settings

(recommended network node capacity 200 nodes)

Slew rate limited transceivers for improved network performance MODBUS Register Summary Table

• DO NOT USE CROSSOVER CABLES. THIS MAY DAMAGE THE CONTROL CARD OR RENDER IT NON-OPERATIONAL.

MODBUS Register Specifications:

Register

Name

R/W Values & Defaults

Units

Origin

Comments

1

RUN/STOP

RW

0,1

1

RAM

power up from REG 14

2

DEMAND

RW

0-100

%

RAM

power up from REG 10

6

SPEED

R

0,5-2000

RPM

LIVE

9

STATUS

R

see detail

-

LIVE

10

DEFAULT SPEED

RW

0-100

50

EEPROM

applies to network only

12

CURRENT SPEED

R

0-100

-

LIVE

14

DEFAULT RUN/STOP

RW

0,1

1

EEPROM

applies in network mode only

To reset non-volatile registers to factory default values, write 170 (AA hex) to Register 14, and then cycle power.