Mac 10, Ledc, 4x4 fan filter unit – Envirco MAC 10 LE-DC User Manual

Page 15

Advertising
background image

MAC 10

®

LEDC

4x4 Fan Filter Unit

15

Innovators in Clean Air Technology | www.envirco.com | Operation & Maintenance

I n s t a l l a t i o n & S e r v i c e M a n u a l

Service: Standard and RSR Motor Removal and Installation

Tools Required: Phillips Head Driver, Battery Operated Drill, (2) 8” adjustable wrenches, 10 mm hex head wrench,

#2 screwdriver, and slip joint pliers

Step 1. To gain access to the motor, remove the ceiling panel next to the unit, if applicable.

Step 2. Switch the ON-OFF switch to the off position.

Step 3. Loosen the electrical box cover screws (2), and slide/lift off cover.

Step 4. Make note of all wire routing and locations for later reinstallation.

Step 5. Disconnect 4-pin and 5-pin wire harnesses from the electrical box housing and remove the tubing for test port, if

installed.

Step 6. Remove the twelve mounting screws to free the motor/blower assembly from the lid assembly. If using power

drivers, set the unit to a low torque setting to avoid stripping the sheet metal screws. Carefully remove housing assembly,

paying attention to wire routing.

Step 7. Unwire the control cap by removing the cap cover and unplugging the cable connector to the motor from inside, then

pull back through the grommet next to the motor. Rubber grommet will need to be removed for connection clearance.

Step 8. Remove the six 10 mm bolts from the motor mounting plate to motor housing assembly.

Step 9. Using one adjustable wrench, loosen the hex nut that attach the blower wheel to the motor shaft while holding motor

shaft still with the second wrench. Remove blower wheel from motor shaft and the c-clip for reuse with new motor.

Step 10. Remove the motor mounting hardware from the backside of the motor mounting plate. Replace with the new motor

and reassemble by reversing the above order.

WARNING

DISCONNECT THE UNIT FROM THE ELECTRICAL

POWER SOURCE BEFORE ATTEMPTING

ANY SERVICE

WARNING

ELECTRICAL SERVICE SHOULD ONLY

BE PERFORMED BY A LICENSED

OR QUALIFIED ELECTRICIAN.

Motor/Electrical Removal

Motor Assembly

Motor Housing

Assm.

Motor Mounting Plate

10 mm bolts

Mounting

Screws

Motor Mounting

Hardware

Motor Mounting

Plate

Motor Shaft

Hex Nut

Motor

Blower

Wheel

C-Clip

Wiring

Grommet

Advertising