Carrier AQUAZONE 50VQP084-300 User Manual

Page 10

Advertising
background image

10

Each unit must be installed with its own individual trap,

vent and means to flush or blow out the condensate drain line.

Do not install units with a common trap or vent. See Fig. 25.

Consider the following:

• Units are typically installed directly above each other on

successive floors with condensate drains located near the

units.

• Connect the unit condensate drain connection to the

building condensate drain with a 1-in. (25 mm) drain

line.

• The horizontal run of a condensate hose is usually too

short to cause drainage problems, however the horizontal

run pitch of the condensate line should be at least 1 cm

for every 50 cm of run in the direction of flow. Avoid low

points and unpitched piping since dirt collects in low or

level areas and may cause stoppage and overflow.

• Install a condensate trap at each unit with the top of

the trap positioned below the unit condensate drain

connection.

• Design the length of the trap (water-seal) based upon the

amount of positive or negative pressure on the drain pan.

As a rule, 25 mm of trap is required for each 10 Pa of

negative pressure on the unit.

VENTING — A vent should be installed in the condensate

line of any application which may allow dirt or air to collect in

the line. Consider the following:

• Always install a vent where an application requires a

long horizontal run.

• Always install a vent where large units are working

against higher external static pressure and to allow

proper drainage for multiple units connected to the same

condensate main.

• Be sure to support the line where anticipated sagging

from the condensate or when “double trapping” may

occur.

• If condensate pump is present on unit, be sure drain con-

nections have a check valve to prevent back flow of con-

densate into other units.

Step 7 — Pipe Connections —

Depending on the

application, there are 3 types of WSHP piping systems to choose

from: water loop, ground-water and ground loop. Refer to the

Carrier System Design Manual for additional information.

All WSHP units utilize low temperature soldered female

pipe thread fittings for water connections to prevent annealing

and out-of-round leak problems which are typically associated

with high temperature brazed connections. Refer to Table 1 for

connection sizes. When making piping connections, consider

the following:

• A backup wrench must be used when making screw con-

nections to unit to prevent internal damage to piping.

• Insulation may be required on piping to avoid condensa-

tion in the case where fluid in loop piping operates at

temperatures below dew point of adjacent air.

• Piping systems that contain steel pipes or fittings may

be subject to galvanic corrosion. Dielectric fittings may

be used to isolate the steel parts of the system to avoid

galvanic corrosion.

WATER LOOP APPLICATIONS — Water loop applications

usually include a number of units plumbed to a common pip-

ing system. Maintenance to any of these units can introduce air

into the piping system. Therefore, air elimination equipment

comprises a major portion of the mechanical room plumbing.

The flow rate is usually set between 2.41 and 3.23 L/m per

kW of cooling capacity. For proper maintenance and servicing,

pressure-temperature (P/T) ports are necessary for temperature

and flow verification.

In addition to complying with any applicable codes, consid-

er the following for system piping:
• Piping systems utilizing water temperatures below

10.0 C require 13 mm closed cell insulation on all piping

surfaces to eliminate condensation.

• All plastic to metal threaded fittings should be avoided

due to the potential to leak. Use a flange fitted substitute.

• Teflon tape thread sealant is recommended to minimize

internal fouling of the heat exchanger.

• Use backup wrench. Do not overtighten connections.

• Route piping to avoid service access areas to unit.

• The piping system should be flushed prior to operation to

remove dirt and foreign materials from the system.

GROUND-LOOP APPLICATIONS — Temperatures be-

tween –3.9 and 43.3 C and a cooling capacity of 2.41 to

3.23 L/s per kW are recommended. In addition to comply-

ing with any applicable codes, consider the following for

system piping:
• Piping materials should be limited to only polyethylene

fusion in the buried sections of the loop.

• Galvanized or steel fittings should not be used at any

time due to corrosion.

• All plastic to metal threaded fittings should be avoided

due to the potential to leak. Use a flange fitted substitute.

• Do not overtighten connections.

• Route piping to avoid service access areas to unit.

• Pressure-temperature (P/T) plugs should be used to mea-

sure flow of pressure drop.

GROUND-WATER APPLICATIONS — Typical ground-

water piping is shown in Fig. 26. In addition to complying

with any applicable codes, consider the following for sys-

tem piping:
• Install shut-off valves for servicing.

• Install pressure-temperature plugs to measure flow and

temperature.

NOTE: Trap should be deep enough to offset maximum unit static
difference.

Fig. 25 — Trap Condensate Drain

*3/4" IPT

Trap Depth

1.5" [38mm]

Min 1.5"

[38mm]

1/4" per foot

(21mm per m)

drain slope

3/4" PVC or

Copper by others

Vent

Fig. 24 — Install Condensate Drain

a50-8486

Advertising