EVCO EVXV815P7 Installer manual User Manual

Page 39

Advertising
background image

EVCO S.p.A.

EVXV 800 range | Installer manual ver. 1.2 | Code 144XV800E124

page 39 of 66

d1

0

3

- - - -

1

1

type of defrosting

0 = electrical (the compressor will be

switched off during defrosting, the

defrosting output will be activated and

the evaporator fan will be switched off)

1 = hot gas (the compressor will be

switched on during defrosting, the

defrosting output will be activated and

the evaporator fan will be switched off)

2 = air (the compressor will be switched off

during defrosting and the defrosting

output

will

be

activated;

the

evaporator fan will be switched on,

independently from the conditions of

the door, i.e. independently from the

door micro switch input status)

3 = air with door open (the compressor will

be switched off during defrosting and

the defrosting output will be activated;

the evaporator fan will be switched on,

on condition that the door is open, i.e.

that is on condition that the door micro

switch is active and that the parameter

i0 is set at values different to 0)

d2

-50.0

99.0

°C/°F (1)

2.0

2.0

defrosting

end

temperature

(evaporator

temperature); also see parameter d3

d3

0

99

min

30

30

if parameter P4 is set at 0, duration of

defrosting

if parameter P4 is set at 1, maximum

duration of defrosting; see also parameter d2

0 = defrosting will never be activated

d4

0

1

- - - -

0

0

defrosting on start-up of blast chilling and

deep freezing

1 = yes

d5

0

99

min

30

30

defrosting delay on start-up of storing

0 = defrosting will be started on expiry of

the time established with parameter

d0