EVCO EPH4EXP Hardware manual User Manual

Page 82

Advertising
background image

EVCO S.p.A.

c-pro 3 | Hardware manual ver. 3.2 | Codice 114CP3E324

page 82 of 116

Networks / CAN

Bus

MyNode

1

127

- - -

1

local (or of the controller) CAN node address

Networks / CAN

Bus

Master

- - -

- - -

- - -

YES

enabling the operation as master in a CAN

network

YES

= yes

Networks / CAN

Bus

Baud

- - -

- - -

- - -

20K

CANbus communication baud rate

20K

= 20,000 baud

50K

= 50,000 baud

125K

= 125,000 baud

500K

= 500,000 baud

Networks / CAN

Bus

Timeout

1

60

s

5

remote (or with a device in the network)

CANbus communication time-out (after this

time without CANbus communication with a

device, it is excluded by the network)

Networks / CAN

Bus

NetworkNode

[ 1 ] 0

[ 32 ]

127

- - -

[ 1 ] 99

address of a remote (or of a device in the

network) CAN node; example for [ 1 ] 2:

[ 1 ]

= node

2

= node’s address

Networks / CAN

Bus

[ press button

RIGHT to

show it ]

TSEG1

0

63

- - -

31

reserved

Networks / CAN

Bus

[ press button

RIGHT to

show it ]

TSEG2

1

7

- - -

7

reserved

Networks / CAN

Bus

[ press button

RIGHT to

show it ]

SJW

0

3

- - -

0

reserved

Networks / CAN

Bus

[ press button

RIGHT to

show it ]

BTR(1)

1

15

- - -

15

reserved