6 =

48.0 sec.

/8

0

1

---

1

unit of measure

It establishes the unit of measure of the parameters expressed in degrees, as indicated:

0 =

the unit of measure is the Fahrenheit degree

1 =

the unit of measure is the Celsius degree.

LABEL MIN. MAX. U.M. ST.

CONNECTION IN A SERIAL NETWORK WITH EVCOBUS

PROTOCOL COMMUNICATION

L1

1

15

---

1

instrument address

It establishes the address to which the instrument (slave) answers when it is connected to a

serial network with EVCOBUS protocol communication managed from a master (for instance a

Personal Computer).
L2

0

7

---

0

instrument group

It establishes the group to which the instrument (slave) answers when it is connected to a

serial network with EVCOBUS protocol communication managed from a master (for instance a

Personal Computer).
ADDITIONAL INFORMATIONS
-

the symbol (*) indicates that the unit of measure depends from the parameter /8.

ALARMS

ALARMS
If the instrument displays the indication “E2” flashing (corrupted memory data alarm) it means

that there is a corruption of the configuration data in the memory (turn OFF and turn ON again

the instrument: if to the turning ON again the alarm does not disappear the instrument must be

replaced); during this alarm the access to the configuration parameters setting procedure is

refused.
If the instrument displays the indication “E0” flashing (probe failure alarm) it means that: the

kind of connected probe is not proper (see the parameter /0), the probe is faulty (verify the

probe integrity), there is a mistake in the instrument-probe connection (verify the instrument-

probe connection integrity), the temperature read by the probe is outside the limits permitted

by the probe in use (verify that the temperature near the probe be inside the limits permitted by

the probe); inactive.
If the instrument displays the indication “99” flashing (end of scale display) it means that the

temperature read by the probe is outside the working range permitted by the instrument (verify

that the temperature near the probe be inside the limits permitted by the instrument); inactive.
ADDITIONAL INFORMATIONS
-

the alarm codes are related in order of precedence.

TECHNICAL DATA

TECHNICAL DATA
Case:

plastic black (PC-ABS), self-extinguishing.

Size:

74 x 32 x 65 mm (2.91 x 1.25 x 2.55 in.).

Installation:

panel mounting, panel cutout 71 x 29 mm (2.79 x 1.14 in.),

with the equipped screw or spring brackets.

Type of protection:

IP 54.

Connections:

screw terminal blocks with pitch 5 mm (0.19 in., power

supply and measure input) for cables up to 2.5 mm² (0.38

in.²), five poles single line male connector with pitch 5.08

mm (0.2 in., serial port).

Ambient temperature:

from 0 to +60 °C (+32 to +140 °F, 10 ... 90 % of not con-

densing relative humidity).

Power supply:

230 Vac or 115 Vac, 50/60 Hz, 1 VA.

Insulation class:

II.

Measure inputs:

1 configurable for PTC/NTC probes.

Working range:

from -50 to +99 °C (-58 to +99 °F) for PTC probe, from

-40 to +99 °C (-40 to +99 °F) for NTC probe.

Resolution:

1 °F with unit of measure in Fahrenheit, 1 °C with unit of

measure in Celsius.

Display:

2-digit display 12.5 mm (0.49 in.) high red LED display

with automatic minus sign.

Serial port:

TTL with EVCOBUS protocol communication, for the con-

nection to the CLONE configurer/cloner and RICS supervi-

sion systems.

HOW TO ORDER

CODING SYSTEM
Instrument name:

EC 3-T60.

Desired measure input:

P (for PTC/NTC probes).

Desired power supply:

220 (230 Vac)

115 (115 Vac).