EVCO EC6105 User Manual

Page 2

Advertising
background image

DEFROST MAXIMUM LENGTH SETTING
To modify the defrost maximum length value to position the microswitch M4 on the desired

scale and to rotate the trimmer TR2 as long as the arrow indicates the desired value (for in-

stance to set a defrost maximum length of twenty-seven minutes to position the microswitch

M4 in position B and to rotate the trimmer TR2 as long as the arrow indicates the notch

12/27).
ADDITIONAL INFORMATIONS
-

the modification of the defrost maximum length value has not immediate effect; to

obtain this effect it must not be executed during the course of the value

-

the course of the defrost maximum length value gets recorded each 10 minutes

and it is stored in a non volatile memory even if a lack of power supply happens;

when the power supply recovers the instrument reproposes the last setting stored

-

if the defrost stopping digital input is activated the instrument never activates a

defrost cycle.

EVAPORATOR FANS STOPPAGE LENGTH SETTING
To modify the evaporator fans stoppage length to rotate the trimmer TR1 as long as the arrow

indicates the desired value (for instance to set an evaporator fans stoppage length of eight

minutes to rotate the trimmer TR1 as long as the arrow indicates the notch 8).
ADDITIONAL INFORMATIONS
-

the modification of the evaporator fans stoppage length value has not immediate

effect; to obtain this effect it must not be executed during the course of the value

-

the course of the evaporator fans stoppage length value gets recorded each 10

minutes and it is stored in a non volatile memory even if a lack of power supply

happens; when the power supply recovers the instrument reproposes the last set-

ting stored.

CONFIGURABILITY

CONFIGURABILITY

CONFIGURABILITY

CONFIGURABILITY

CONFIGURABILITY

CONFIGURABILITY
MIN. MAX. U.M. ST.

DEFROST REGULATOR

0

7

---

3

number of automatic defrost cycles in the course of the

24 hours

It establishes the number of automatic defrost cycles that the instrument activates in the course

of the 24 hours.
0

30

min. 30

defrost maximum length

It establishes the defrost maximum length.
MIN. MAX. U.M. ST.

EVAPORATOR FANS REGULATOR ASSOCIATED TO THE

OUTPUT K 1

0

10

min. 10

evaporator fans stoppage length

It establishes the time that disable the output activation from the moment of the defrost end.

SIGNALS

SIGNALS

SIGNALS

SIGNALS

SIGNALS

SIGNALS
If the LED L1 is turned ON it means that the output K 1 is activated.
If the LED L2 is turned ON it means that the output K 2 is activated.
If the LED L2 flashes it means that an evaporator fans stoppage is running.

TECHNICAL DA

TECHNICAL DA

TECHNICAL DA

TECHNICAL DA

TECHNICAL DAT

TT

T

TA

A

A

A

A

TECHNICAL DATA
Case:

plastic grey (PP0), self-extinguishing.

Size:

53 x 90 x 58 mm (2.08 x 3.54 x 2.28 in., 3 DIN modules).

Installation:

on DIN EN 50022 standard rail installation according with

DIN 43880 norms.

Type of protection:

IP 40.

Connections:

screw terminal blocks with pitch 7.5 mm (0.29 in., power

supply, digital input and outputs) for cables up to 2.5 mm²

(0.38 in.²).

Ambient temperature:

from 0 to +60 °C (+32 to +140 °F, 10 ... 90 % of not con-

densing relative humidity).

Power supply:

230 Vac or 115 Vac or 24 Vac, 50/60 Hz, 1.5 VA.

Insulation class:

II.

Digital inputs:

1 for the remote stopping of a defrost (5 V, 1 mA) with NC

contact.

Display:

output status indicators.

Outputs:

two 8 (2) A @ 250 Vac relays for evaporator fans (NO con-

tact) and defrost system (change-over contact) manage-

ment.

Defrost management:

interval, safety temperature and maximum length.

HOW TO ORDER

HOW TO ORDER

HOW TO ORDER

HOW TO ORDER

HOW TO ORDER

CODING SYSTEM
Instrument name:

EC 6-105.

Fixed:

D.

Desired power supply:

220 (230 Vac)

115 (115 Vac)

A24 (24 Vac).

Options:

custom configuration.

2

3

Advertising