EVCO EC7133 User Manual

Ec 7-133, On-off single output digital thermoregula- tor, General informations

Advertising
background image

EC 7-133

ON-OFF single output digital thermoregula-

tor

Operating instructions
Release 1/99 of March the eleventh 1999
Code EC 7-133 DOC E000
File 7133e.p65
IMPORTANT:
The use of this new instrument is easy; but for safety reasons, it is

important read these instructions carefully before the installation or

before the use and follow all additional informations.
It is very important keep these instructions with the instrument for future

consultations.

ENGLISH

GENERAL INFORMATIONS

WHAT IS THE USE
EC 7-133 is an ON-OFF single output digital thermoregulator able to cover a temperature range

from -99 to +999 °C (-99 to +999 °F).
In factory the instrument gets preset to accept at the measure input PTC/NTC probes or “J”/

”K” thermocouples or 2/3 wires Pt 100 probes or 2 and 3 wires 0/4-20 mA temperature trans-

ducers (in this last case it is possible to set the reading scale).
Some parameters permit to set the thermoregulator for “cooling” or “heating” functioning, to

protect the connected load against overloads due to several starts repeated in a short time, to

signal working conditions outside the safety limits.
EC 7-133 is available in the 72 x 72 mm (2.83 x 2.83 in.) case and it is studied for panel

mounting with the equipped U-bracket.

GETTING STARTED

INSTALLATION
EC 7-133 was studied for panel mounting, panel cutout 68 x 68 mm (2.67 x 2.67 in.), with the

equipped U-bracket (the overall dimensions and the panel cutout are related in Fig. 3, the fixing

system suggested by the builder is related in Fig. 4).
ADDITIONAL INFORMATIONS
-

the panel thickness must be included from 1 to 5 mm (0.04 to 0.19 in.)

-

verify if the using conditions (ambient temperature, humidity, etc.) are within the

limits indicated by the builder (see the chapter TECHNICAL DATA)

-

install the instrument in a location with a suitable ventilation, to avoid the internal

overheating of the instrument

-

do not install the instrument near surfaces that can to obstruct the air-grating (car-

pets, covers, etc.), heating sources (radiators, hot air ducts, etc.), locations sub-

ject to direct sunlight, rain, humidity, excessive dust, mechanical vibrations or

bumps, devices with strong magnetos (microwave ovens, big speakers, etc.)

-

according with the safety norms, the protection against possible contacts with

electrical parts and parts protected with functional insulation only must be ensured

through a correct installation procedure of the instrument; all parts that ensure the

protection must be fixed so that they can not be removed if not with a tool.

ELECTRICAL CONNECTION
EC 7-133 is provided with one extractable screw terminal block for cables up to 2.5 mm²

(0.38 in.², for the connection to the power supply, measure input and output), located on the

instrument back panel (the connections to derive are related in Fig. 5 and they are checkable on

the polyester label stuck on the instrument case).
ADDITIONAL INFORMATIONS
-

if the instrument is brought from a cold to a warm location, the humidity may con-

dense inside the instrument; wait about an hour before supply the instrument

-

verify if the operating power supply voltage, electrical frequency and power of the

instrument correspond to the local power supply (see the chapter TECHNICAL

DATA)

-

do not supply more instruments with the same transformer

-

if the instrument is installed on a vehicle, its power supply must be derived directly

from the battery of the vehicle

-

give the instrument a protection able to limit the current absorbed in case of failure

-

the instrument remains connected to the local power supply as long as the termi-

nals 9 and 10 are derived to the local power supply, even if the instrument is appar-

ently turned off

-

give the probe a protection able to insulate it against possible contacts with metal

parts or use insulated probes

-

give the output a protection able to protect it against short circuit and overload

-

do not try to repair the instrument; for the repairs apply to highly qualified staff

-

if you have any questions or problems concerning the instrument please consult

Every Control (see the chapter BUILDER DATA).

Fig. 1

f7-133.wmf

USE

PRELIMINARY INFORMATIONS
After derived the connections related in Fig. 5, during the normal functioning the instrument

displays the temperature read by the probe.

Fig. 2

iu7133.wmf

If an alarm should be active the instrument displays the alarm code flashing and the buzzer

utters an intermittent beep as long as the cause that has given it does not disappear (see the

chapter SIGNALS AND ALARMS); pressure on the key T1 during an alarm permits to silence

the buzzer.
EC 7-133 is provided with one working setpoint and with some configuration parameters that

get stored in a non volatile memory and that permit to set the instrument according with one’s

requirements (see the chapter CONFIGURABILITY).
The output K 1 is associated to the working setpoint, it remains activated continuously as long

as the temperature read by the probe reaches the working setpoint and when it rises above (if

the output was set for “cooling” functioning) or it falls below (if the output was set for “heating”

functioning) the working setpoint of the hysteresis value (differential) the output gets reacti-

vated.

WORKING SETPOINT SETTING (WORKING TEMPERATURE)
To modify the working setpoint value keep pushed the key T3 (the instrument displays the

actual value) and at the same time push and release over and over the key T1 or T2 as long as

the instrument displays the desired value (keeping pushed the key T1 or T2 the value gets

decreased or increased more quickly): after the modification release the key T3 last; during the

pressure of the key T3 the LED L1 flashes quickly to indicate that a working setpoint setting

procedure is running (to the release of the key T3 the instrument automatically turns out from

the working setpoint setting procedure).
ADDITIONAL INFORMATIONS
-

for the whole period of a corrupted memory data alarm the access to the working

setpoint setting procedure is refused

-

the working setpoint is programmable within the limits established with the param-

eters rA1 and rA2

-

if the parameter rA5 has value 1 the working setpoint can not be modified as long as

the parameter rA5 gets set to 0

-

the working setpoint value gets stored in a non volatile memory even if a lack of

power supply happens.

CONFIGURATION PARAMETERS SETTING
Configuration parameters are arranged on two levels, to protect the most tricky settings against

undesirable violations and they are arranged in families that can be recognized through the

initial letter of the label.
To gain access to the first level keep pushed at the same time for four seconds at least the keys

T1 and T2 (passed four seconds the instrument displays the label PA).
To select a parameter of the first level push and release over and over the key T1 or T2 as long

as the instrument displays the label of the desired parameter.
To modify the parameter value keep pushed the key T3 (the instrument displays the actual

value) and at the same time push and release over and over the key T1 or T2 as long as the

1

DIMENSIONAL DATA

OVERALL DIMENSIONS AND PANEL CUTOUT
The dimensions are expressed in millimetres and inches (fourth-scale drawing).

Fig. 3

ds7e.wmf

INSTALLATION

WITH THE FIXING SYSTEM SUGGESTED BY THE BUILDER
Panel mounting, with the equipped U-bracket (fourth-scale drawing).

Fig. 4

ms7.wmf

ELECTRICAL CONNECTION

CONNECTIONS TO DERIVE
Instance of typical application.

BUILDER DATA

EVERY CONTROL S.r.l.
Via Mezzaterra 6, 32036 Sedico Belluno ITALY
Phone 0039/0437852468 (a.r.) Fax 0039/043783648
Internet addresses
e-mail: [email protected]
http://www.everycontrol.it

TO BE CAREFUL
This publication exclusively belongs to EVERY CONTROL and shall not be reproduced and distributed if not expressly authorized by the same EVERY CONTROL.
EVERY CONTROL does not assume any responsibility in order to the characteristics, to the technical data and to the possible mistakes related herein or deriving from the use of the same.
EVERY CONTROL can not be considered responsible for damages caused from the inobservance of the additional informations.
EVERY CONTROL reserves the right to make any modification without prior notice and at any time without prejudice the basic functioning and safety characteristics.

Fig. 5

c7-133e.wmf

4

Advertising