Static Pressure Controller Installation Instructions

Avoid locating the front of the static pressure controller in sun light or other areas with high ambient light
or corrosive levels. Bright light shining on the photocells can cause false actuation of the load relays.

The static pressure controller should be zeroed out before attaching the low and high pressure hoses.
The zero adjustment is located between the minimum and maximum dials.

Using the supplied rubber tubing the high side of the static pressure controller should be plumbed to the
inside of the building. The low side of the static pressure controller should be plumbed to the A306
outdoor sensor. See the A306 installation instructions.

A306 Outdoor Sensor

Use the installation instructions shipped with the A306 outdoor sensor.