FloAire STAGED ELECTRIC HEAT MODULE User Manual

Page 18

Advertising
background image

18

Modulating Coil Thermostat Dip Switch Settings

To test and verify all coil circuits during startup, perform the following:

Discharge Control: Disconnect one wire to the discharge air sensor to simulate a call for
maximum amperage.

Space Control: Set the Thermostat dipswitches to discharge control.

Once maximum amperage is achieved and tested, configure wiring and dipswitches to their original state.

Step Controller Coil Thermostat Dip Switch Settings

C1025

Thermostat*

C1025-1000

Thermostat*

T920D-F

Thermostat*

Discharge Control

Discharge Control

Discharge Control

S1

On

S1

On

S1

On

S2

Off

S2

Off

S2

Off

S3

Off

S3

Off

S3

On

Space Heating

Space Heating

Space Heating

S1

Off

S1

Off

S1

Off

S2

On

S2

On

S2

On

S3

Off

S3

Off

S3

On

Step Controller and Thermostat Dip Switch Setting Chart

Thermostat

Step Controller

Input

Step Controller Control

Discharge

Control

S1

Off

S1

On

4 Stage Heating

S1

On

S2

Off

S2

Off

S3

On

S2

Off

S3

Off

S4

On

S4

On

2 Stage Heating

Space Heating

S3

On

5 Stage Heating

S1

Off

S4

Off

S3

Off

S2

On

S4

Off

3 Stage Heating

S5

On

S3

Off

S6

Off

S4

On

8 Stage Heating

S3

On

S4

On

S5

On

S6

Off