Grounding the Units

Grounding the Units

Ensure that the system is grounded properly. The units contain a number of static sensitive components that can
be damaged by static discharge.

IMPORTANT: An Earth Ground Rod is Strongly
Recommended
and should be no further than 12
feet from the unit and use a minimum of 12
gauge wire in most cases. The type and length of
earth ground rods vary by region. Contact the
building inspector’s office in the municipality
where you plan to install the unit for correct
grounding materials and installation
procedures.

Other Ground Sources

within 12 ft of Unit

Green Ground

Wire

Earth Ground Rod

Ground to

Existing

Electrical

System

Electrical

Panel

Ground to

Metallic Cold

Water Pipe

12 ft Maximum

12 AGW Minimum

1

2

3

4

5

6

7

8

9

AUG 10, 2005

WELCOME

1

2

3

4

10

11

5

6

7

8

9

10

12

11

OR

NOTE: Keep ground wire as
straight as possible.

Before digging, contact your local
utility companies, to avoid
damaging gas, power, or other
underground utility lines.

DO NOT ground the units to a
pedestal post (gooseneck) if
one is used.