Wire Specs and Run Distances

Wire Specs and Run Distances

Use this chart to pull wires in preparation of your installation:

Power Wire Specs and Run Distances

Description of Wire Run

Grounding the Chassis

Residence and Telco Phone Lines

Door Strike

Magnetic Lock

Dry Contact Closure (Most Gate Operators)

Exit Request (REX) / Auxiliary Open Devices

AutoCall

Door Status Sensor

Barium Ferrite and Wiegand Readers

Proximity Readers

Radio Frequency Module (RF)

Postal Lock

CCTV Camera (Optional)

Wire Specification

12 AWG Copper

2 Twisted Pairs

18-24 AWG Shielded

2-Conductor

18-22 AWG Shielded

2-Conductor

18-22 AWG Shielded

2-Conductor

18-24 AWG Shielded

2-Conductor

18-24 AWG Shielded

2-Conductor

18-24 AWG Shielded

2-Conductor

18-24 AWG Shielded

5-Conductor

18-24 AWG Shielded

5-Conductor

22 AWG Shielded

RG-6 Coaxial

75 ohm

2-Conductor

18-24 AWG Shielded

Single Conductor

RG-59u Coaxial

Maximum Distance

12 feet

5000 feet*

500 feet

500 feet

100 feet

1000 feet

(Monitor with a .25 volt

p-p composite signal

sensitivity)

Page

8

9-14

15

15

16

16

17

17

18

18

18

19

19

NOTE: Use metal conduit - run wires in metal conduit instead of PVC pipe. Wires run in PVC conduit may
experience interference. Metal conduits also add extra protection against lightning strikes.
Never run Telco Wires and High Voltage wires in the same conduit. The high voltage may interfere with the Telco
Wires, possibly causing the system to malfunction.
* Total distance from Telco to residence regardless of number of units in chain.

Distance

Under 30 Feet

30 - 75 Feet

75 - 250 Feet

12 VAC Power (Included)

2-Conductor Shielded

14 AWG

14 AWG

14 AWG

12 VDC Power (Not Provided)

2-Conductor Shielded

14 AWG

14 AWG

N/A

Always provide power from a dedicated source. Plug provided transformer into an outlet wired to its own 10 AMP
minimum circuit breaker. This will prevent two problems:
• Other equipment cannot introduce spikes, noise, surges or dips into the power circuit that will affect the system.
• The system’s operation will not be affected if any other equipment develops a short circuit across the power line.

CAUTION: Not responsible for conflicts between the information listed in the above table and the requirements of
your local building codes. The information is for suggested use only. Check your local codes before installation.