Vpd design considerations, Diagnostic leds – Interlogix VDP-ESP Series User Manual

Page 7

Advertising
background image

P/N 1069686 • REV 1.0 • ISS 10MAR10

7 of 11

VPD Design Considerations

Step 1: Measure or calculate the distance from each camera to the DVR (DVideo).

Step 2: Calculate Maximum possible distance from each camera to power supply
(DPower) using the Power/Distance Chart:

• If (DVideo) < 750 feet AND (DVideo) < (DPower)

Use a combiner transceiver at Control Room.

• If (DVideo) > 750 feet

Use a combiner at Mid-span location closer to the cameras.

Use an active receiver hub at control room.

Step 3: Use a single channel GE combiner transceiver on the camera side
considering the camera voltage.

Diagnostic LEDs

GEC-4VDPBC, GEC-16VDPBC:

There is one green LED per channel:

OFF: Camera power is disconnected

ON: Camera is connected and current flows

GEC-8PVPDTCHUB, GEC-16PVPDTCHUB:

There are two diagnostic LEDs per channel:

Green LED:

OFF: Camera power is disconnected

ON: Camera is connected and current flows

Red LED:

OFF: The fuse is blown

ON: Power is available at RJ-45 connector to the Camera