KTP-24-8 Multiple Output Power Supply Installation

Instructions

O

PERATION

Table 1. Maximum cable length

Maximum Cable Length

Wire Gauge

All Domes
without Heater/Fan
(20VA)

10 2.60

3000

915

12 2.05

1900

580

14 1.62

1200

365

16 1.29

750 230

18 1.02

465 142

20 0.81

290 90

22 0.64

185 56

Each 24 VAC output of the power supply has a resettable fuse that will trip
if the current draw exceeds one amp. In this event, the device on that
output may operate intermittently, or not at all. The fuse will automatically
reset itself when the load is removed from the output.

CAUTION:
Do not reconnect any device that caused an output fuse to trip until
the device has been inspected and determined to be in proper
working condition.