2 restricted range current output modes (4-20 ma) – Campbell Hausfeld 4-Channel Current/Voltage SDM-CVO4 User Manual

Page 23

Advertising
background image

Instruction Manual

7: -1666.67 B3
8: 10

A4

9: -5000

B4


; Now update the SDM-CVO4 with the information
; for the four channels

11: SDM-AO4 (P103)
1: 4

Reps

2: 30

SDM

Address

3: 5

Loc [ ScldOut_1 ]

6.2.2 Restricted Range Current Output Modes (4-20 mA)

When driving a system that requires a restricted current range then the full-scale
range is reduced accordingly. In the case of 4-20 mA devices the maximum range
is 8000 units and the minimum value should be scaled to
-3000 and prevented from going below this level.

The following partial program could be used in place of the last two instructions
in the example above.

; Then apply the scaling with one instruction P53
; The readings are scaled -3000 to +5000, i.e. to
; cover the range which would equate to
; 4-20 mA in current mode.

; Windspeed to cover the range 0-100 m/s
; Wind direction to cover 0-360 degrees
; Temperature -25 to +50 degrees C
; Radiation 0 - 1000 m^2/s

10: Scaling Array (A*Loc+B) (P53)
1: 5

Start Loc [ ScldOut_1 ]

2: 80

A1 ; WS multiplier

3: -3000

B1 ; WS Offset

4: 22.2222 A2
5: -3000

B2

6: 106.667 A3
7: -333.32 B3
8: 8

A4

9: -3000

B4


; Now limit the lowest scaled value to -3000 (4 mA)
; As we have four 4-20 mA current outputs, a loop
; construct is the easiest way to do this.

11: Beginning of Loop (P87)
1: 0000

Delay

2: 4

Loop

Count


; If the scaled value is less the –3000

12: If (X<=>F) (P89)

1: 5

-- X Loc [ ScldOut_1 ]

2:

4

<

3:

-3000 F

4: 30

Then Do

17