Table 2 -- Electrical Data -- Units Without Optional Convenience Outlet (cont)

UNIT

50PG

NOMINAL

POWER SUPPLY

Volts-Ph-Hz

VOLTAGE

RANGE

COMPRESSOR

OFM

FLA

POWER

EXHAUST

FLA

IFM

TYPE

IFM

FLA

ELECTRIC HEAT

POWER SUPPLY

DISCONNECT

SIZE

Min

Max

RLA

LRA

FLA

Nominal

kW*

MCA

MOCP†

FLA

LRA

07

(cont)

208/230-3-60

187

253

20.5

149

1.5

1.4

Low

5.2

33.7/33.7

35/35

33/33

184/184

10.0/11.5

3.8/ 5.0

33.7/33.7

35/35

33/33

184/184

15.0/17.3

5.6/ 7.5

33.7/33.7

35/35

33/33

184/184

20.0/23.1

7.5/10.0

33.7/37.1

35/40

33/34

184/184

30.0/34.6

11.3/15.0

45.8/51.5

50/60

42/47

184/184

40.0/46.2

15.0/20.0

58.3/66.0

60/70

54/61

184/184

50.0/57.7

18.8/25.0

70.8/80.4

80/90

65/74

184/184

High

7.5

36.0/36.0

40/40

36/36

210/210

10.0/11.5

3.8/ 5.0

36.0/36.0

40/40

36/36

210/210

15.0/17.3

5.6/ 7.5

36.0/36.0

40/40

36/36

210/210

20.0/23.1

7.5/10.0

36.1/40.0

40/45

36/37

210/210

30.0/34.6

11.3/15.0

48.6/54.4

50/60

45/50

210/210

40.0/46.2

15.0/20.0

61.1/68.9

70/70

56/63

210/210

50.0/57.7

18.8/25.0

73.6/83.3

80/90

68/77

210/210

460-3-60

414

506

9.6

75

0.8

Low

2.6

15.4

20

15

92

5.8

5.0

15.4

20

15

92

8.7

7.5

15.4

20

15

92

11.5

10.0

17.6

20

16

92

17.3

15.0

24.9

25

23

92

23.1

20.0

32.1

35

30

92

28.9

25.0

39.4

40

36

92

High

3.4

16.2

20

16

105

5.8

5.0

16.2

20

16

105

8.7

7.5

16.2

20

16

105

11.5

10.0

18.6

20

17

105

17.3

15.0

25.9

30

24

105

23.1

20.0

33.1

35

30

105

28.9

25.0

40.4

45

37

105

0.6

Low

2.6

16.0

20

16

93

5.8

5.0

16.0

20

16

93

8.7

7.5

16.0

20

16

93

11.5

10.0

18.4

20

17

93

17.3

15.0

25.6

30

24

93

23.1

20.0

32.9

35

30

93

28.9

25.0

40.1

45

37

93

High

3.4

16.8

20

17

106

5.8

5.0

16.8

20

17

106

8.7

7.5

16.8

20

17

106

11.5

10.0

19.4

20

18

106

17.3

15.0

26.6

30

24

106

23.1

20.0

33.9

35

31

106

28.9

25.0

41.1

45

38

106

575-3-60

518

633

7.6

54

0.8

Low

2.0

12.3

15

12

67

9.2

10.0

14.0

15

13

67

13.9

15.0

19.9

20

18

67

18.5

20.0

25.6

30

24

67

23.1

25.0

31.4

35

29

67

27.7

30.0

37.1

40

34

67

High

2.8

13.1

15

13

78

9.2

10.0

15.0

15

14

78

13.9

15.0

20.9

25

19

78

18.5

20.0

26.6

30

24

78

23.1

25.0

32.4

35

30

78

27.7

30.0

38.1

40

35

78

1.4

Low

2.0

13.7

15

14

69

9.2

10.0

15.8

20

14

69

13.9

15.0

21.6

25

20

69

18.5

20.0

27.4

30

25

69

23.1

25.0

33.1

35

30

69

27.7

30.0

38.9

40

36

69

High

2.8

14.5

15

14

80

9.2

10.0

16.8

20

15

80

13.9

15.0

22.6

25

21

80

18.5

20.0

28.4

30

26

80

23.1

25.0

34.1

35

31

80

27.7

30.0

39.9

40

37

80

LEGEND

FLA

--- Full Load Amps

HACR --- Heating, Air Conditioning and Refrigeration

IFM

--- Indoor (Evaporator) Fan Motor

LRA

--- Locked Rotor Amps

MCA --- Minimum Circuit Amps

MOCP --- Maximum Overcurrent Protection

NEC

--- National Electrical Code

OFM --- Outdoor (Condenser) Fan Motor

RLA

--- Rated Load Amps

*Heater capacity (kW) is based on heater voltage of 208v, 240v, 480v, or 600v. If power

distribution voltage to unit varies from rated heater voltage, heater kW will vary accord-

ingly.
{

Fuse or HACR circuit breaker.

NOTES:

1. In compliance with NEC requirements for multimotor and combination load equipment (refer

to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or

HACR breaker. Canadian units may be fuse or circuit breaker.

2.

Unbalanced 3-Phase Supply Voltage

Never operate a motor where a phase imbalance in supply voltage is greater than 2%. Use

the following formula to determine the percentage of voltage imbalance.

% Voltage Imbalance

= 100 x

max voltage deviation from average voltage

average voltage

Example: Supply voltage is 230---3---60

AB = 224 v

BC = 231 v

AC = 226 v
Average Voltage = 224 + 231 + 226

3

681

3

=

227

=

Determine maximum deviation from average voltage.

(AB) 227 – 224 = 3 v
(BC) 231 – 227 = 4 v

(AC) 227 – 226 = 1 v
Maximum deviation is 4 v.

Determine percent of voltage imbalance.

% Voltage Imbalance

= 100 x

4

227

= 1.76%

This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.

IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric
utility company immediately.