Coleman Echelon FC9V User Manual

Page 4

Advertising
background image

246786-CTG-B-0407

4

Unitary Products Group

FILTER PERFORMANCE

The airflow capacity data published in the “Blower Perfor-
mance” table listed above represents blower performance
WITHOUT filters. To determine the approximate blower per-
formance of the system, apply the filter drop value for the fil-
ter being used or select an appropriate value from the “Filter
Performance” table shown.

NOTE: The filter pressure drop values in the “Filter Perfor-
mance” table shown are typical values for the type of filter
listed and should only be used as a guideline. Actual pres-
sure drop ratings for each filter type vary between filter manu-
facturer.

APPLYING FILTER PRESSURE DROP TO
DETERMINE SYSTEM AIRFLOW

To determine the approximate airflow of the unit with a filter in
place, follow the steps below:

1.

Select the filter type.

2.

Determine the External System Static Pressure (ESP)
without the filter.

3.

Select a filter pressure drop from the table based upon
the number of return air openings or return air opening
size and add to the ESP from Step 2 to determine the
total system static.

If total system static matches a ESP value in the airflow table
(i.e. 0.20, 0.60, etc,) the system airflow corresponds to the
intersection of the ESP column and Model/Blower Speed row

.

FILTER SIZES

Input / Output

BTU/H

CFM

Cabinet

Size

Top Return

Filter in

60/56

1200

B

(2) 14 x 20

80/75

1200

B

(2) 14 x 20

80/75

1600

C

(2) 14 x 20

100/95

2000

C

(2) 14 x 20

120/112

2000

D

(2) 14 x 20

FILTER PERFORMANCE - PRESSURE DROP INCHES W.C.

Airflow Range

Minimum

Opening Size

Filter Type

Disposable

Washable Fibers

Pleated

CFM

in

2

In W.C.

In W.C.

In W.C.

0 - 750

230

0.01

0.01

0.15

751 - 1000

330

0.05

0.05

0.20

1001 - 1250

330

0.10

0.10

0.20

1251 - 1500

330

0.10

0.10

0.25

1501 - 1750

380

0.15

0.14

0.30

1751 - 2000

380

0.19

0.18

0.30

2001 & Above

463

0.19

0.18

0.30

UNIT CLEARANCES TO COMBUSTIBLES

Application

Top

Front

Rear

Left Side

Right Side

Flue

Floor/Bottom

Closet

Alcove

Attic

Line Contact

In.

In.

In.

In.

In.

In.

In.

Downflow

1

3

0

0

0

0

1

*

Yes

Yes

Yes

NA

Horizontal

0

3

0

1

1

0

0

Yes

Yes

Yes

Yes

*

Combustible floor base or air conditioning coil required for use on combustible floor.

Advertising