Contactor fails to energize – Chromalox PQ402-6 User Manual

Page 3

Advertising
background image

If the contactor fails to energize, check for blown fuses in

the control circuit. If the fuses are not blown, check the contac-
tor holding coil. The holding coil can be checked by jumpering
Terminal L1 of the line and Terminal No. 4 (coil lead) on the
contactor. See Figure 1.

A. If the contactor fails to energize, then the coil is defective.
B. If the contactor energizes, it is an indication of failure in

either the Pressure Control or in the McDonnell-Miller three
wire mercury switch.

Pressure

Control

Setting

Differential

Control

Setting

Bellows

Syphon

Tube

Since the Pressure Control and the three wire mercury switch

are wired in series, they can be checked one at a time by placing
a jumper across each control. If the mercury switch or Pressure
Control fail to energize, check the McDonnell-Miller controls by
jumpering Terminals 5 and 6. See Figure 2.

At this point, the contactor should energize unless there is an

open wire in the control circuit.

PRESSURE CONTROL — Malfunctions in the pressure control
can be mechanical or electrical.

The bellows should be removed and the small orifice at the

bottom cleaned out. The bellows must be replaced if it is punc-
tured. The syphon tubing should also be cleaned by steam while
the control is removed; it will be necessary to join the two loose
leads in order to activate the boiler. See Figure 3.

The electrical controls should be checked by referring to the

Contactors, Elements and Voltages section.

NOTE: If control is purchased locally, remove #8-32 orifice
screw.

Figure 3 — Pressure Control

Figure 2 — Low Water Cut-Off Junction Box

Figure 1

CONTACTOR FAILS TO ENERGIZE

Advertising