Figure 2: Tamper Switch Installation

3.0

TRB Wiring Instructions

Refer to Figure 1 on page 1 for all instructions in this Section.

Tamper Switches

provides the input signal for enclosure tamper events – enclosure cover forced open and/or
enclosure removed from its mounting location

uses normally-open switches

connection is made to either or both J3 and J5 (the switch connections are designed in parallel)

requires two-conductor, AWG 22 wire

Bypass Jumpers

used if a tamper switch is NOT used in one of the two switch positions (single-switch application)

factory default is jumpers ON (bypasses both Tamper Switches)

remove the corresponding jumper when a tamper switch is installed
-

remove Bypass Jumper 1 (J4) for switch position 1 (J3)

-

remove Bypass Jumper 2 (J6) for switch position 2 (J5)

Relay Contacts

completes the circuit for alarm annunciation

relay changes state as a tamper switch changes state

Keri does NOT provide the alarm annunciation device

requires two- or three-conductor, AWG 22 wire depending upon your alarm annunciation device

Unit Power

requires 12 VDC, can be tapped off of the controller’s power

requires two-conductor, AWG 22 wire

Enclosure

Wall

Tamper

Switch

Switch

Plunger

Switch

Connection

Wires

Outside of

Enclosure