Nxt 4x4, Installation guide – Keri Systems NXT 4x4 User Manual

Page 3

Advertising
background image

NXT 4x4

Installation Guide

Page 3 of 4

P/N: 01998-001 Rev. G

Table 2: Reader and 4x4 Cable Options

Connection Type

Total

Run

Length

Shielded, Stranded,

2 Twisted-Pair

a

a. Keri recommends this cable type for best system performance.

CAT-5

b

b. Keri’s preferred low-cost option. Keri has no suggested vendor for this type of cable.

Shielded, Stranded,

4-Conductor

c

c. Use care when routing this type of cable as it can make the system more susceptible to EMI.

AWG

Suggest

AWG

Suggest

RS-485 bus

from NXT-2D/-4D

to NXT-4x4 only

up to

500 feet

18 - Data plus

4x4 Power

22 - Data only

Belden

8723

unshielded

18 - Data plus

4x4 Power

22 - Data only

Windy City:

414302-S

West Penn: 244

Tappan:

1880AB4M-CM

RS-485 bus

from NXT-2D/-4D

to NXT-4x4

and NXT Readers

up to

500 feet

18 - Data plus

4x4 Power

22 - Data only

Belden

8723

shielded

18 - Data plus

4x4 Power

22 - Data only

Windy City:

414302-S

West Penn: 244

Tappan:

1880AB4M-CM

RS-485 bus

from NXT-2D/-4D

to NXT Readers only

up to

1,000 feet

22 for Data

Belden

8723

shielded

22 for Data

Windy City:

416303-S

West Penn: 241

Tappan:

2280AB4M-CM

Table 3: Controller Power, Inputs, and Outputs Cable Requirements

Connection

Total Run

Length

# of

Conductors

Shielded

Stranded

Twisted

Pair

AWG

Belden

Equivalent

controller power

250 feet

a

a. To meet CE and C-tick regulations, the length of the controller power line can be no longer than 3 Meters

(9.85 feet).

2

N

Y

Y

18

8461

earth ground

shortest

path

b

b. Use the shortest possible path from earth ground point to PCB. Connect the earth ground only to the

designated pin on the terminal block. This is important as all transient protection for the unit is made through
this earth ground connection. For unit protection, the earth ground connection should always be made first.

1

N

N

n/a

18

no specific

requirement

inputs and outputs

c

c. Values listed are minimums. Individual input and output devices may have more specific requirements.

500 feet

2

N

Y

n/a

22

no specific

requirement