LAARS POWER VENTED GAS WATER HEATER - Installation Manual User Manual

Page 13

Advertising
background image

13

Venting (Part I) continued-

THROUGH THE WALL VENTING: (HORIZONTAL VENTING)
Cut a 3 1/2 in. (8.9 cm) diameter hole in the wall at the point where the vent
connector is going to pass through the wall. Use the proper cement to secure
the 90° vent terminal provided with the water heater to the vent connector. The
distance between the edge of the 90° vent terminal and the exterior wall (see
Figure 3) must be 1 in. (2.5 cm). Use the proper cement and assembly
procedures to secure the vent connector joints between the terminal and the
blower outlet. Provide support brackets for every 5 feet (1.5m) of horizontal
vent.

4” VENT INSTALLATION

3” VENT INSTALLATION

Figure 3