Mc rear view – LAARS MC4EXT - Install and Operating Manual User Manual

Page 2

Advertising
background image

LAARS HEATING SYSTEMS

Page 2

1.2 Mounting the Output Cards

The Output Cards are mounted on the rear of the

MCX (see Figure 1).

Each Output Card controls two stages. The two

stages connected to one Output Card must have the
same type of output (135

Ω, 0-5V, 1-5V, 0-10V, 2-

10V, or 4-20mA). However, different types of Output
Cards can be combined on the MCX, and each Output
Card can be programmed differently.

Align the Output Card with the pins on the back

of the panel and gently press them on until the top of
the pins appear through the Output Card connector.

1.4 Attaching the Connecting Cable

to the MC

Remove the MC from its enclosure.
Secure the remaining Header cable to the

enclosure as described above.

On the rear of the MC, locate JP4 and attach the

three screw terminal connector.

Return the panel to its enclosure, replace the top

screw, and tighten the bottom two screws.

Reattach the Panel-to-Panel cable to the Header

cables.

1.5 Wiring the Power

Bring the 120VAC 60Hz power wires through a

bottom Knockout of the enclosure. The right front
Knockout is preferred.

Class 1 voltages must enter the enclosure

through a different opening from any Class 2 voltage
wiring.

Connect the hot line to terminal marked LINE.
Connect the neutral line to the terminal marked

NEUT.

The green ground screw MUST be connected to

earth ground (see Figure 5).

1.3 Attaching the Connecting Cable

to the MCX

Disconnect the Panel-to-Panel cable from the

two Header cables (see Figure 3).

Remove a Knockout from the enclosure.
Insert the end of the Header cable with three

screw terminals through the Knockout into the interior
of the enclosure.

Use the mounting holes to secure the square end

of the Header cable to the enclosure.

Connect the three screw connector to the black

header on the rear of the MCX marked J12 (see
Figure 1).

Return the panel to its enclosure, replace the top

screw, and tighten the bottom two screws.

1.6 Installing the Output Relays

Each output stage (E through L) which is to be

used must have a relay installed in the socket. These
relays are ordered separately (p/n CA002300).

To install a relay, orient the pins and then press it

gently into the appropriate socket.

Any stage output which does not have a relay

must have its Mode set to Off (see MC I/O manual,
Stage Settings).

1.7 Wiring the Stage Outputs

Each Stage output (E through L) has one

Normally Open (N.O.) relay contact.

The N.O. contacts are dry contacts only. They do

not source any voltage.

Each N.O. contact is capable of switching 6A

resistive at 120VAC.

Total output of all stages must not exceed 15A.
Wire the N.O. relay contacts in series with the

unit’s limit circuit (see Figure 6).

Figure 3. Cable Connections.

Panel-to-Panel Cable

Mounting

holes

Header

Cabl

e

To header

MCX

or

MCX

J12

JP4

Figure 4. MC Rear View.

MC REAR VIEW

JP4

Output C&D

Output A&B

Fuse

Figure 5. Power Wiring.

SAFETY

GROUND

MUST BE

CONNECTED

Earth

Ground

Neutral

Line

120VAC

60 Hz

Advertising