Cascading multiple boilers


You can cascade up to eight NeoTherm boilers together. One boiler becomes the Master and

the other boilers become the Slaves.

Note:
The system sensor and outdoor sensor will need to be wired to the Master boiler only.
The input from these sensors is used by the Master control to control the modulation rate of all

of the operating boilers it is connected to. If the Outdoor sensor is not used, the alarm light on

the SOLA control will be on, and the alarm contacts will close.

Lead Lag Set Point

Navigation

Home screen, press “I” Info/Install button

Scroll to “Advanced Set Up”, press OK

Scroll down to highlight “Lead Lag Configure”, press OK

“Lead Lag Master Configure” is highlighted, press OK

Scroll down to “Setpoint”, press OK

Adjust the setpoint, press OK (see bottom of page 5)

Lead Lag Outdoor Reset

Navigation

Home screen, press “I” Info/Install button

Scroll to “Advanced Set Up”, press OK

Scroll down to highlight “Lead Lag Configure”, press OK

Scroll Down to highlight “Lead Lag Outdoor Reset”, press OK

Note: The Outdoor Reset is already Enabled. You may choose to adjust the other set points

Use the Down button to highlight each parameter you wish to change

Press OK, change the desired set point, press OK.

Use the Down button to choose your next set point, make adjustments, press OK

Warm Weather Shut Down

Navigation

Home screen, press “I” Info/Install button

Scroll to “Advanced Set Up”, press OK

CH Configure, Press OK

Use the Down button to highlight “Warm Weather Shutdown”, press OK

Highlight Warm Weather Shutdown Setpoint”, press OK

Adjust the set point, press OK