Section x: maintenance, General, Danger – LAARS U.H.E. - Installation Manual User Manual

Page 39

Advertising
background image

SECTION X: MAINTENANCE

DANGER

DO NOT ATTEMPT TO REPAIR GAS VALVE.
DO NOT ATTEMPT TO REPAIR IGNITION MODULE.
DO NOT ATTEMPT TO REPAIR VENTURI.
DO NOT ATTEMPT TO REPAIR THERMOSTAT BOARD.
DO NOT ATTEMPT TO REPAIR TRANSFORMER.
DO NOT ATTEMPT TO REPAIR PRESSURE SWITCH.

GENERAL


KEEP APPLIANCE AREA CLEAR AND FREE FROM COMBUSTIBLE MATERIALS, GASOLINE AND OTHER
FLAMMABLE VAPORS AND LIQUIDS.

Water heater maintenance includes periodic tank flushing and cleaning, and removal of lime scale. The unit should be
inspected and adjusted to maintain proper combustion. Refer to Table 5, “Suggested Maintenance Schedule”. A
periodic inspection of the venting system should be made.

MAINTENANCE SCHEDULE

Following are the instructions for performing some of the recommended maintenance. Unit inspection and adjustment
should be performed by a competent technician.

Suggested Maintenance Schedule

COMPONENT

OPERATION

INTERVAL

REQUIRED

Tank Sediment

Removal Monthly Flushing

Anode Rods

Inspect

Semi-Annually

Replace as

Required

Relief Valve

Check Operation

Semi-Annually

Proper

Operation

Blower

Clean Inlet Screen

As Required

Soft Brush

Vent & Air

Intake System

Inspect Every

3

Months

Joints should

be sealed

Ignition System

Inspect

Annually

Clean of dust

and dirt

Vent Terminal

Free of Shrubs &

Debris

Monthly

Remove object

that caused

restriction

Combustion

System

Inspect Monthly

Confirm

S-OP

Condensate

Line

Inspect Monthly

Remove

restriction

Table 5.

FLUSHING WATER HEATER

1. Turn OFF the water heater electrical disconnect switch.
2. Open the drain valve and allow water to flow until it runs clean.
3. Close the drain valve when finished flushing.
4. Turn ON the water heater electrical disconnect switch.

39