Mighty Therm LO-NOx Volume Water Heater

Page 7

Table 2. Air Openings to Outside.

Required Net Free Opening Area

Directly from Outside

At Top

At Bottom

Model

in.

2

cm

2

in.

2

cm

2

250

63

406

63

406

400

100

645

100

645

Note: For screens or louvers, add 50%.

Figure 20. Indoor Installation and Venting.

Notes:
1.

The drafthood must sit directly on top of the heater
as shown and must not be altered in any manner.

2.

A vent cap listed or certified for the application by a
Nationally Recognized Testing Laboratory (NRTL)
such as Underwriter’s Laboratories (UL) is required to
eliminate downdraft and to allow the heater to function
properly.

3.

Use approved roof fitting.

Vent terminated at
least 2 ft. (61cm)
above any
object within
10 ft. (3.0m)

10 ft.
3.0m

2 ft. 61cm

Listed Vent

Cap

Storm Collar

Roof Jack

Drafthood

1/4 in. 0.6cm
Minimum Pitch
Per Foot of
Horizontal Pipe

Figure 19. Base for Outdoor Installation.

Figure 18. Outdoor Location Installation.

Figure 17. Incorrect Outdoor Installation.

WINDOW

OR GRILL

INDOOR

ROOM

4 ft.

1.2m

10 ft.
3.0m

4 ft.

1.2m

LAARS

UNIT

(Side View)

2.4 Combustion and Ventilation

Air Supply

All indoor installations must have openings to

outside air for combustion, ventilation and dilution of
flue gases from inside the building (see Figure 20 and
Table 2 ). Laars does not recommend indoor
installations that do not provide combustion air from
outside the building.

In the United States, the most common

requirements specify that the space (enclosure) shall
communicate with the outdoors in accordance with
method 1 or 2, which follow. Where ducts are used,
they shall be of the same cross-sectional area as the
free area of the openings to which they connect.

Method 1:

Two permanent openings, one commencing

within 12" (30 cm) of the top and one commencing
within 12" (30 cm) of the bottom of the enclosure shall
be provided. The openings shall communicate
directly, or by ducts, with the outdoors or spaces that
freely communicate with the outdoors. When directly
communicating with the outdoors, or through vertical
ducts, each opening shall have a minimum free area of
1 square inch per 4000 Btu/hr (550 square mm/kW) of
total input rating of all equipment in the enclosure.
When communicating to the outdoors through

123456789012345678901234567890121234567890123456789012345678901212345

123456789012345678901234567890121234567890123456789012345678901212345

123456789012345678901234567890121234567890123456789012345678901212345

123456789012345678901234567890121234567890123456789012345678901212345

123456789012345678901234567890121234567890123456789012345678901212345

12345678901234567890123

12345678901234567890123

12345678901234567890123

Base For Outdoor Unit

Adequate

Air Supply

To Room

Top and

Bottom

5 ft.

min.

1.5m

Forced Air Inlet

Minimum Clearances

4 ft.

1.2m

3 ft.

0.9m

horizontal ducts, each opening shall have a minimum
free area of not less than 1 square inch per 2000 Btu/hr
(1100 square mm/kW) of total input rating of all
equipment in the enclosure.