Mini-Therm II Hydronic Boiler

Page 5

2.2 Field Assembly

1.

Mini-Therm II boilers have built-in draft diverter
for natural draft operation.

2.

Find the vent damper box which is located in the
boiler package.

3.

Install the vent damper directly to the top of the
draft diverter outlet with the damper operator
facing to the front of the boiler, and with the
flow direction arrow pointing upward. Use the
vent damper wire harness provided with the
boiler to connect the vent damper to the boiler.
The bracket end of the harness should be
connected to the vent damper actuator.

4.

For Model JVS only: Install the metal plug
provided with the vent damper onto the damper
plate hole. Disregard the metal plug in case of
standing (continuous) pilot boilers. For all JVT
models, the damper plate hole should never be
blocked.

5.

Do not modify the automatic vent damper
device. It is very important that no other vents
are closed. Provide at least six inches clearance
between the automatic vent damper and
combustible construction, and be sure to allow
access for servicing the damper.

6.

Install the temperature/pressure gauge provided
in the parts box.

Figure 1. Dimensional Information.

Vent Damper
optional in Canada

Front

View

Top

View

Left

Side

View

B

D

V

E

9-1/4

24

7

18

17-3/4

451

Vent Damper
Harness

1-1/4 NPT

Draft

Diverter

A/2

C

A

In Return

T&P Gauge

Out Supply

PRV

Dimensions in inches cm

Dimensions

Water

Gas

inches cm

Conn.

Conn.

Size*

A

B

C

D

E

V

in.

in.

50

13-3/8 34

27-3/4 71

23-5/8 60

21-3/4 55

26-1/2 67

4 10

1-1/4

1/2

75

13-3/8 34

27-3/4 71

24-1/8 61

21-3/4 55

27-1/2 70

5 13

1-1/4

1/2

100

16-7/8 43

28-3/4 73

24-1/8 61

22-3/4 58

27-1/2 70

5 13

1-1/4

1/2

125

16-7/8 43

28-3/4 73

23-5/8 60

22-3/4 58

27-1/2 70

6 15

1-1/4

1/2

160

20-3/8 52

28-3/4 73

23-5/8 60

22-3/4 58

27-1/2 70

6 15

1-1/4

1/2

225

25-5/8 65

31-1/2 80

23-1/4 59

23-3/4 63

27-1/2 70

7 18

1-1/4

*

3/4**

* Values shown are for both JVS and JVT Models

**1/2 for propane

Figure 2. Field Assembly Items.

Vent
Damper
Harness

Vent
Damper

Draft
Diverter

(built-in)

Temp
Press
Gauge