LAARS Mini-Therm JVi - Install and Operating Manual User Manual

Addendum to mini-therm jvi manual

Advertising
background image

Mini-Therm JVi Venting Material

10-27 December 14, 2010


To:

Manufacturer’s Representatives, Distributors, Contract Service Centers, Regional Sales Managers

and Internal Departments

From: Tom Gervais, International Sales Director

There has been an instance of confusion regarding suitable venting material for use on the Mini-Therm JVi
product within Canada. Therefore, the table used in section “1H-2: Horizontal Venting – Category III” of the
Mini-Them manual has been updated to more clearly indicate what is an allowable vent material.

In Canada: Use "BH-Type" vent materials certified to ULC-S636 Class I (more than 135°C, but not more
than 245°C flue gas temperature), made of AL29-4C stainless steel or equal.
'RQRWXVHSODVWLFYHQWLQJRIDQ\NLQG

800.900.9276 • Fax 800.559.1583 (Customer Service, Service Advisors)

20 INDUSTRIAL WAY, ROCHESTER, NH 03867 • 603.335.6300 • Fax 603.335.3355 (Technical Support)

1869 SISMET ROAD, MISSISSAUGA, ONTARIO, CANADA L4W 1W8 • 905.238.0100 • Fax 905.366.0130

Addendum to Mini-Therm JVi Manual

This Addendum applies to the following Documents:

Models Affected

Sizes

Part No.

Doc. No.

Mini-Therm JVi, JVH

50-225

H2020900D

Doc. 1080D

Page 8

Change to Column 2 Table:

1H-2. Horizontal Venting - Category III
(a) Vent Connections

Materials

Vent Length

In U.S.A.: UL type 304, 316 or 294-C

Up to a maximum

stainless steel, 26 gauge minimum.

of 55' (17m) of

In Canada: Use "BH-Type" vent

equivalent pipe

materials certified to ULC-S636

run (including

Class I (more than 135°C, but not

required elbows).

more than 245°C flue gas
temperature), made of AL29-4C
stainless steel or equal.

Do not use plastic venting of any kind.