Reverse actuator hod reassembly – Leslie Controls DIAPHRAGM ACTUATOR 135(R) User Manual

Page 11

Advertising
background image

11

2.

Screw handscrew (4) into the bonnet as far as it
will go.

3.

Remove nuts and bolts (18,19 see Fig 3) from
upper diaphragm case (14).

4.

Lift diaphragm case (14) while moving the case to
one side so that handscrew disc assembly can be
disengaged from diaphragm nut (8) by passing it
through the slot in the diaphragm nut. (see Fig 4)

5.

Remove handscrew (4) from bonnet (7).

NOTE: Clean all parts and replace any that are worn or
damaged.

Reverse Actuator HOD

Reassembly

(see Fig 3)








1.

Insert handscrew (4) into bonnet (7) and screw
down through bonnet threads.

2.

Insert diaphragm case (14) making sure that
handscrew disc assembly is engaged to diaphragm
nut (8). (see Fig 4)

3.

Tighten nuts and bolts (18,19 see Fig 3) into upper
diaphragm case (14).

4.

Screw handscrew (4) up through bonnet (7).

5.

Place handwheel (3) over stem. Install lockwahser
(2) and tighten nut (1).

Act. Size (see
Fig 1)

Lower Dia.
Casing Bolts (23,24)

Upper Dia. Casing
Bolts (18,19)

35R

15-20

15-20

55R/55AR

30-36

15-20

85R/85AR

30-36

15-20

135R

45-50

15-20

Table 4 - Torque Values (ft-lbs)


Size

1

6

35R

15-20

3-5

55R/55AR

15-20

15-20

85R/85AR

15-20

15-20

135R

30-36

15-20

Table 5 – Torque Values Hand Operating Device (ft-lbs)







NOTE

Ensure that all components being installed are free
from any nicks burrs or defects prior to assembly.