Leslie Controls CONTROL VALVES DLOS-2 & DDLOS-2 (150/300) User Manual

Page 7

Advertising
background image

7

actuator over valve plug stem and bolts (9)

to top of packing bearing (12). Secure with

two nuts (7) finger tightened.

14.

Secure Actuator flange to bonnet flange with

Cap Screws.

15.

With wrench on flats of valve stem, lift

valve plug (2) and with counter-clockwise

motion engage threads in upper stem (31) of

actuator until valve plug can be turned no

more.



SETTING VALVE TRAVEL
CLASSES: DLO-2 AND DLOS DIRECT
ACTING ACTUATOR
(See Fig. 7 in Appendix)

1.

Connect controlled air line to diaphragm

case connector.

2.

Supply 3 PSIG air pressure to actuator

diaphragm.

3.

Compress actuator spring by turning spring

adjustor (35) until travel indicator (37) just

starts to move when air pressure is raised

above 3 PSIG.

NOTE: Alternately add compression and check
starting pressure slightly above 3 PSIG until
correct adjustment is attained. After each check
return air pressure to 3 PSIG.

4.

Actuator spring preload adjustment can be

made either with or without pressure in

valve body. Once correct compression is

made no further adjustment is necessary.

5.

With valve plug and coupling threads

engaged supply 20 PSIG operating pressure

to actuator diaphragm. Valve will move to

closed position. Observe travel obtained as

shown by travel indicator and indicator

scale. Read- just as follows:

6.

OVERTRAVEL – If travel is too great,

loosen stem locknut and turn valve plug

stem out of coupling the amount necessary

to obtain correct travel.

7.

UNDERTRAVEL – (Travel is too short)

This is not possible if prior step 15 was done

and correct parts were used.

8.

When correct travel has been obtained

reduce operating pressure sufficiently to

move valve plug away from seat ring. Then

turn valve stem one full turn out of upper

stem threads. Secure locknut.

9.

The one full turn toward the seat ring, made

after obtaining travel, provides the positive

closing force required to obtain tight valve

closure. In all cases be sure to make this

final adjustment.

10.

Tighten locknut. Reconnect operating

medium tubing from the sensing element or

manual loading device to the diaphragm

case.


SETTING VALVE TRAVEL

CLASSES: DDLO & DDLOS REVERSE
ACTING ACTUATOR
(See Fig. 9 in Appendix)

1.

Connect controlled air line to diaphragm

case connection.

2.

Supply 3 PSIG air pressure to actuator

diaphragm.

3.

Compress actuator spring until travel

indicator begins to move when air pressure

is raised above 3 PSIG.

NOTE: Alternately add compression and check
starting pressure slightly above 3 PSIG until
correct adjustment is attained. After each check
return air pressure to 3 PSIG.

4.

The valve plug is closed against upward

fluid thrust by actuator spring force. Total

compression placed on actuator spring must

be sufficient to provide the 3 PSIG preload

plug force required to close the valve.

5.

If preload adjustment is made with no

pressure in valve body, then, when the

control valve is placed in operation,

additional compression must be placed on

the actuator spring to provide valve closure

force. With proper adjustment valve will

Advertising