Table 13 — keyboard directory (cont) – Carrier 39L User Manual

Page 73

Advertising
background image

Table 13 — Keyboard Directory (cont)

SERVICE CONFIGURATIONS

Keyboard Entry

Display

Description

COOLCOIL

Configuration of cooling
(chilled water coil or DX)

MPG X

Master proportional gain

MIG X

Master integral gain

MDG X

Master derivative gain

SMG X

Submaster gain

SCV X

Submaster center value

HHL X

High humidity limit

SMR X

Submaster reference value

SMR X

Submaster reference value forced

DXCOOL

Configure DX cooling

SMG X

Submaster gain

SMG X

Submaster gain forced

MSR X

Minimum submaster reference

DX1G X

Stage 1 Time Guard

device

DX2G X

Stage 2 Time Guard

DX3G X

Stage 3 Time Guard

DX4G X

Stage 4 Time Guard

DX5G X

Stage 5 Time Guard

DX6G X

Stage 6 Time Guard

DX7G X

Stage 7 Time Guard

DX8G X

Stage 8 Time Guard

DX1T X

Stage 1 logic type

DX2T X

Stage 2 logic type

DX3T X

Stage 3 logic type

DX4T X

Stage 4 logic type

DX5T X

Stage 5 logic type

DX6T X

Stage 6 logic type

DX7T X

Stage 7 logic type

DX8T X

Stage 8 logic type

INLET GV

Configuration of inlet guide vanes

MPG X

Master proportional gain

MIG X

Master integral gain

MDG X

Master derivative gain

SMG X

Submaster gain

SCV X

Submaster center value

SMR X

Submaster reference value

SMR X

Submaster reference value forced

DX

Direct Expansion

OAVP — Outside Air Velocity Pressure

SERVICE CONFIGURATIONS

Keyboard Entry

Display

Description

MIXADMPR

Configuration of mixed air damper

MPG X

Master proportional gain

MIG X

Master integral gain

MDG X

Master derivative gain

SMG X

Submaster gain

SCV X

Submaster center value

MDP X

Minimum damper position

SMR X

Submaster reference value

SMR X

Submaster reference value forced

DPSP X

Damper set point

DPSP X

Damper set point forced

OAE X

Outside air enthalpy

RAE X

Return air enthalpy

CNTRL X

Damper controlled by

ELECHEAT

Configuration of electric heat

MPG X

Master proportional gain

MIG X

Master integral gain

MDG X

Master derivative gain

SMG X

Submaster gain

SMR X

Submaster reference value

SMR X

Submaster reference value forced

NTFC

Configuration of nighttime
free cooling (NTFC)

NTLO X

NTFC lockout temperature (minimum
outside air temperature to operate
NTFC)

NPURGE

Configuration of night purge

NPMN X

Night purge duration

NPDL X

Night purge low temperature
damper position

NPDH X

Night purge high temperature
damper position

MDP X

Minimum damper position

OAC

Configuration of constant
outside air

MPG X

Master proportional gain

MIG X

Master integral gain

MDG X

Master derivative gain

SMG X

Submaster gain

SMG X

Submaster gain forced

OALV X

OAVP sensor low voltage point

OAHV X

OAVP sensor high voltage point

OALR X

OAVP sensor low voltage reference

OAHR X

OAVP sensor high voltage reference

PMF X

OAVP sensor probe multiplier factor

MDP X

Minimum damper position

SMR X

Submaster reference value

SMR X

Submaster reference value forced

73