5.3 Calibrating the Slant Valve

The roll (slant) valve can only be calibrated manually as described below. When calibrating the
roll valve, calibrate the deadzone clockwise and counter clockwise settings first and then the

gain clockwise and counter clockwise settings.

Navigating to the Slant Valve Settings:
1. Ensure the UC4.5 control panel is in manual mode and at the run screen.

2. Press

until the display shows "More?". Press

to confirm.

3. Press

until the display shows "Roll?". Press

to confirm.

4. Press the

button to access the next menu prompt or press

to access the previous

menu. Choose the dead zone up/down or gain up/down setting (Figure 2).

Roll Channel On

Roll Channel Dead Zone Clockwise (CW)

Roll Channel Gain Clockwise (CW)

Roll Channel Dead Zone Counter Clockwise (CCW)

Roll Channel Gain Counter Clockwise (CCW)

Figure 2: Slant Valve Settings

Manual Dead Zone Calibration:
1. Follow Section 5.2 Step 1 (level booms, working RPM, etc.) before proceeding.

2. Choose the dead zone up or down setting (Figure 2).

3. Press and hold the

button.

4. The valve will turn on at the indicated setting for exactly one-second. The screen will show

the actual change in height.

KP

5

KP

5

Roll OnU

DZ 20

DZ 20

Sensor

Display

Setup