15.2 Sensors

Height or roll sensor appears not to work (displays “NO COMM”):
 This may be caused by a damaged or defective CANbus cable. Ensure all cables are

connected correctly. The connections should be tight and free of corrosion.

 If the cables check out ok the sensor may be damaged. Try swapping sensors to see if the

problem follows the sensor.

Invalid height sensor measurement (displays “NO DATA”):
 It is normal to see this message occasionally. If you are seeing this message all the time the

sensor may be having difficulty obtaining a proper reading. Ensure the sensor is not out of
range. Check the sensor alignment. The sensor should point almost perpendicular to the
ground and there should be no obstructions between the sensor and the ground.

 The protective foam shield may be contaminated. Inspect and clean the foam shield. If it is

severely worn or dirty replace the foam shield.

 The sensor may have moisture in it. This can be common for sprayers which fold the wing

tips up; therefore pointing the sensors into the air. If rain or moisture collects in the
sensor, remove the protective foam disc and allow the water to drain out. If you leave the
sensor running it will dry out on its own and start working again.

 The sensor transducer may be damaged. Remove the foam shield and check if you can hear

the sensor ticking. If you cannot hear the ticking sound or if it is very faint then the
transducer may be damaged and the sensor would need repairing.

Swapping Sensors:

 Turn the system power off.

 Disconnect the existing sensor. Connect the new sensor.

 Cycle the power twice (turn on and off). The sensor will not work properly if this step is

neglected.

 Turn system power on.