Model 1077-wa, Warning, Installation instructions – Oberon 1077-WA User Manual

Page 2

Advertising
background image

*




Step 4 – Remove the ceiling tile
from the location where the
access point enclosure is to be
placed

(if

necessary)

and

replace with the assembled unit
(ref. Figure 6). Use a minimum
of two separate grid wires to
attach

the

access

point

enclosure to the ceiling. Attach
one end of the wire to the
eyebolts and the other end to a
permanent structure within the
ceiling such as a ceiling joist.

**IMPORTANT** - This is

an important safety feature
that could prevent human
injury or damage to the
access point should the unit
become dislodged from the
ceiling grid work.





Step 5 – Once the assembly has been installed in the ceiling and secured using grid wire, open the door and run the Ethernet
cable into the enclosure through the conduit nipple located on the side of the access point enclosure and attach to the access
point prior to installing on mounting plate.






Insert foam into the conduit connector and pull the data cable through far enough to allow attachment to the access point (8" -

10"). Tighten cable clamp around foam fire block so that there are no air gaps. Be careful not to over tighten and crush the

Ethernet cable(s).






Page 4

MODEL 1077-WA

Installation Instructions

**** WARNING ****

Please thoroughly read the product warning below

before installation to provide for a safe work

environment.

1. Ceiling mounted products should be installed in accordance with National Electric Code paragraphs 300.10 (Electrical

Continuity of Metal Raceways and Enclosures) and 300.11 (Securing and Supporting). Independent support wires or
other means must be used for the installation of this product in the ceiling. Acoustical, suspended, false, drop and
concealed spline ceiling grid work is not designed to support the weight of this product. Oberon’s ceiling mounted
products have four support wire tabs on the back box. These tabs shall be used for supporting the product with
independent support wires, wire rope, threaded rod, or other secure support means of adequate gauge and fire
resistance.

2. When closing the enclosure access door, be sure that the cam lock is completely engaged to prevent the access door

from accidentally swinging open.

3. When opening the enclosure door, be sure to support the door to prevent the door from accidentally falling open.

4. This enclosure has a maximum operating ambient of 55º C (131º F), the temperature within the enclosure may not

exceed this temperature, depending on power dissipation within enclosure.


5. A minimum air clearance of 1“ between the housing of the access point and the enclosure side walls must be

maintained for the safe operation of the equipment.


6. This product is intended to be installed by trained personnel.

7. Only Listed ITE shall be installed within the enclosure.

8. This product is to be repaired by personnel trained by the manufacturer or returned to the manufacturer for repair or

replacement.


9. Maximum weight to be installed in the unit is 25 lbs.

10. All knockouts, openings, and holes shall be sealed with a plug constructed of metal, or a non-metal material that

complies with UL 2043 or UL 1479.


11. All unused mounting holes should be sealed with tape or other material that complies with UL 1479.

12. If AC power is used inside the enclosure, connect the ground wire to the green ground screw located near the

knockout in the backbox.


Page 1