Make piping connections, Make electrical connections – Carrier POSITIVE PRESSURE STORAGE SYSTEM 19XB User Manual

Page 7

Advertising
background image

Table 3 — 19XB Storage Tank Rated Dry Weight and Refrigerant Capacity

English

SIZE CODE

TANK OD

(in.)

DRY WEIGHT*

(lb)

MAXIMUM REFRIGERANT CAPACITY (lb)

ASHRAE/ANSI 15

UL 1963

R-22

R-134a

R-22

R-134a

0428

24.00

2380

1842

1860

1704

1716

0452

27.25

3460

3527

3563

3264

3286

SI

SIZE CODE

TANK OD

(mm)

DRY WEIGHT*

(kg)

MAXIMUM REFRIGERANT CAPACITY (kg)

ASHRAE/ANSI 15

UL 1963

R-22

R-134a

R-22

R-134a

0428

610

1080

836

844

773

778

0452

592

1569

1600

1616

1481

1491

LEGEND

ANSI

American National Standards Institute

ASHRAE — American Society of Heating, Refrigeration,

and Air Conditioning Engineers

UL

Underwriters’ Laboratories

*The above dry weight includes the pumpout unit weight of 210 lbs (95 kg).

Make Piping Connections —

Figure 6 represents typi-

cal pumpout unit/chiller piping connections. Standard con-
nections for

1

2

-in. OD copper tubing are provided. Install

the field-supplied FPT tee with pipe plug in the piping as
shown in Fig. 6. This tee is used for refrigerant charging.

NOTE: If any field piping runs exceed 50 ft in length, use

7

8

-in. OD copper tubing to minimize pressure drop.

Pumpout unit water piping connections are shown in

Fig. 6. Both connections are

1

2

-in. NPT (female). A shutoff

valve should be installed in the water line. Provide a means
for blowing water from the condenser coil at winter shut-
down to prevent freeze-up damage. Refer to the Job Data for
water piping particulars.

INSTALL VENT PIPING TO RELIEF DEVICES — The
pumpout storage tank is factory-equipped with relief de-
vices. Refer to Fig. 5 and Table 2 for size and location of the
relief devices. Vent the relief devices to the outdoors in ac-
cordance with ANSI/ASHRAE 15 Safety Code (latest edi-
tion) for Mechanical Refrigeration and all other applicable
codes. Relief devices are set to relieve at 300 psig
(2068 kPa).

Refrigerant discharged into confined spaces can dis-
place oxygen and cause asphyxiation.

1. If relief devices are manifolded, the cross-sectional area

of the relief pipe must at least equal the sum of the areas
required for individual relief pipes.

2. Provide a pipe plug near outlet side of each relief device

for leak testing. Provide pipe fittings that allow vent pip-
ing to be disconnected periodically for inspection of valve
mechanism.

3. Piping to relief devices must not apply stress to the de-

vice. Adequately support piping. A length of flexible tub-
ing or piping near the device is essential on spring-
isolated machines.

4. Cover the outdoor vent with a rain cap and place a con-

densation drain at the low point in the vent piping to pre-
vent water build-up on the atmospheric side of the relief
device.

Make Electrical Connections —

See nameplate on

compressor of pumpout unit and Table 1 for motor electrical
data. Wire unit according to the diagram inside the control
box.

Fig. 7 is the wiring schematic for a complete system that

includes the 19XB storage tank and the pumpout unit.
Fig. 8 is the wiring schematic for the pumpout unit. Use this
schematic for installations that do not include an auxiliary
pumpout storage tank.

NOTE: Use copper conductors only.

7

Advertising