WARNING

Failure to understand and follow these installation instructions

and the WARNING notes contained therein may result in severe
personal injury, death or substantial property damage.

1. To reduce the risk of ignition of hazardous atmospheres:

In accordance with the National Electrical Code, do not install
where operating temperature code exceeds the ignition tempera-
ture of the hazardous atmosphere. Use only in atmospheres hav-
ing an ignition temperature higher than 165˚ C (329˚ F).

2. Disconnect from supply circuit before opening enclosures.
3. Hazard of Electric Shock. Heater must be effectively grounded in

accordance with N.E.C. to eliminate shock hazard.

4. Heat exchanger contains Propylene Glycol under pressure at oper-

ating temperature. A material safety data sheet (MSDS) is avail-
able from Chromalox upon request. Should leakage occur,
remove unit from service and investigate cause.

5. Keep all electrical enclosure covers tightly closed and secured

with all bolts and threads. Cover joints must be clean before
replacing covers.

6. Install and operate in upright position only. Refer to Figure 3 for

level requirements. Failure to comply will cause overheating of
the element and shutting down the unit by tripping the high tem-
perature cutout.

7. All unused threaded openings not used for supply wiring must be

fitted with threaded plugs approved for use in hazardous loca-
tions.

8. All unit electrical installation fittings, conduit, wiring and seals

must meet NEC and local codes for hazardous locations.

9. External line fusing or circuit breaker protection is required.
10. Hi limit cutouts must never be bypassed in the control circuit.
11. Alarm pilot lamp, if supplied, will turn on if the high limit control

actuates. Steady on lamp indicates manual reset protector has
tripped. This could result if the heat exchanger is obstructed
(dirty), inlet air restricted or fan not turning. Shut off power to
unit and refer to repair procedures section of instruction sheet.

12. Mounting clearances on nameplate must be observed.
13. Use copper wire for supply connections according to size and rat-

ing on nameplate.

14. Do not install any type of gasket material on any of the electrical

junction box cover surfaces.

15. Do not attempt to override louver stops or operate unit with lou-

vers fully closed.

2

GENERAL

The CXH-A series units rated 3 through 35 kW are designed

for operation in Class I, Div. 1, Groups C & D and Class II, Div.
1, Groups E, F and G hazardous atmospheres having an ignition
temperature of 165˚C (329˚F) or higher. They are designed for
comfort heating and should not be operated in ambient tempera-
tures exceeding 40˚C (104˚F). All units in Table A are UL listed.
The units are easily adapted for wall, ceiling or pole mounting.
Refer to Figure 4 on Page 3 for mounting information. They are

supplied with either 24 or 120V internal control circuit voltage.
The heater is designed for use with an external hazardous location
thermostat or optional built-in thermostat.

The standard heater is designed to operate up to 7500

feet (2,286m) altitude. Consult factory for specific recommen-
dations when using the units at higher altitudes.

Heavy gauge adjustable

louver with minimum

opening stops - to direct air flow

Removable front cover

for ease of cleaning

High efficiency heat

exchanger with integral

aluminum-finned steel tubes

Optional service light to

indicate when unit

needs servicing

Built-in 120V control

circuit transformer

(Optional 24V available)

Heavy duty immersion heater assembly

with manual reset limit control and

NEMA 7 and 9 terminal enclosure

Protective housing

for immersion heater

terminal enclosure

Convenient terminal

block for room

thermostat connection

Motor connections

wiring access

Explosion-proof
(NEMA 7 and 9)

controls enclosure

Integral, heavy duty

magnetic contactor

Explosion

proof motor

Mounting bolt

hanger connections

Polyester powder-coated

heavy gauge steel corrosion

resistant cabinet

Overpressure

protection device