Final installation checks

Installation/Servicing Tools

Changes in the product and components

In the case of an air conditioner using R410A, in order to prevent
any other refrigerant from being charged accidentally, service port

diameter of the outdoor unit control valve (3 way valve) has been
changed. (1/2 UNF 20 threads per inch)
• In order to increase the pressure resisting strength of the

refrigerant piping flare processing diameter and size of opposite
side of flare nuts has been changed. (for copper pipes with
nominal dimensions 1/2 and 5/8)

• Incidentally, the “refrigerant cylinder” comes with the refrigerant designation (R410A) and protector coating in the U,S.’s ARI specified rose

color (ARI color code: PMS 507).

• Also, the “charge port and packing for refrigerant cylinder” require 1/2 UNF 20 threads per inch corresponding to the charge hose’s port

size.

Table: New tools for R410A

New tools for R410A

Applicable to R22 model

Changes

As pressure is high, it is impossible to measure by means of conventional

Gauge manifold

x

gauge. In order to prevent any other refrigerant from being charged, each
port diameter is changed.

In order to increase pressure resisting strength,

Charge hose

x

hose materials and port size are changed (to 1/2 UNF 20 threads per
inch). When purchasing a charge hose, be sure to check the port size.

As pressure is high and gasification speed is fast, it is difficult

Electronic balance

o

to read the indicated value by means of charging cylinder, as air bubbles

for refrigerant charging

occur.

Torque wrench

x

The size of opposite sides of flare nuts have been increased. Incidentally,

(nominal diam. 1/2, 5/8)

a common wrench is used for nominal diameters 1/4 and 3/8.

Flare tool

o

By increasing the clamp bar’s receiving hole, strength of spring in the tool

(clutch type)

has been improved.

Gauge for projection

-

-

adjustment

Used when flare is made with using conventional flare tool.

Connected to the conventional vacuum pump. It is necessary to use an
adapter to prevent vacuum pump oil from flowing back to the charge hose.

Vacuum pump

o

The charge hose connecting part has two ports-one for conventional

adapter

refrigerant (7/16 UNF 20 threads per inch) and one for R410A.
If the vacuum pump oil (mineral) mixes with R410A a sludge may occur
and damage the equipment.

Gas leakage detector

x

Exclusive for HFC refrigerant.