Table 1A — 30MPA Air-Cooled and 30MPW Liquid-Cooled Units — English

* With optional hot gas bypass.

NOTES:

1. Operating weight includes refrigerant operating charge and

weight of fluid in the heat exchangers.

2. 30MPW units are shipped with full operating charge.

UNIT 30MPA,MPW

015

020

030

040

045

NOMINAL TONS

15

20

30

40

45

OPERATING WT (lb)

MPA

626

635

722

913

934

MPW

680

704

862

1099

1190

REFRIGERANT (lb)

R-410A

MPA

MPW

11.6

15.2

23.1

29.4

34.4

COMPRESSOR

Scroll, Hermetic

Quantity

2

2

2

3

3

Speed (rpm)

3500

3500

3500

3500

3500

Compressor Nominal Tons

7.5

10

15

13

15

Oil Charge (pt)

10.6

13.8

13.8

20.6

20.6

Capacity Control — Standard

No. of Steps

2

2

2

3

3

Minimum Step Capacity (%)

50

50

50

33

33

Capacity Control — Optional Hot Gas Bypass

No. of Steps

3

3

3

4

4

Minimum Step Capacity (%)

18

25

34

21

22

EVAPORATOR

Weight (lb, empty)

27.5

40.3

91.8

122.3

128.3

Net Fluid Volume (gal.)

0.8

1.2

2.4

3.2

3.4

Maximum Refrigerant Pressure (psig)

650

650

650

650

650

Maximum Fluid-Side Pressure (psig)

300

300

300

300

300

Water Connections (in.)

Inlet and Outlet (Victualic)

2

2

2

1

/

2

2

1

/

2

2

1

/

2

Drain (NPT)

1

/

2

1

/

2

1

/

2

1

/

2

1

/

2

CONDENSER (30MPW Only)

Weight (lb, empty)

34.9

43.6

104.6

136.7

188.3

Net Fluid Volume (gal.)

1.2

1.6

2.9

4.1

5.9

Maximum Refrigerant Pressure (psig)

650

650

650

650

650

Maximum Fluid-Side Pressure (psig)

300

300

300

300

300

Water Connections (in.)

Inlet and Outlet (Victualic)

2

2

2

1

/

2

2

1

/

2

2

1

/

2

CHASSIS DIMENSIONS (in.)

Length

55

55

55

55

55

Width

32

32

32

32

32

Height

63

63

63

63

63

MINIMUM SYSTEM FLUID VOLUME (gal. per Ton)

Normal Air Conditioning
Standard

6

6

6

4

4

Optional Hot Gas Bypass

4

4

4

3

3

Low Outdoor Ambient Cooling Operation (30MPA Units)
Standard

10

10

10

8

8

Optional Hot Gas Bypass

7

7

7

6

6

CAPACITY STEPS

Step 1

100%

100%

100%

100%

100%

Step 2

50%

50%

50%

67%

67%

Step 3

18%*

25%*

34%*

33%

33%

Step 4

21%*

22%*

MINIMUM FLOW RATES (gpm)

Evaporator

22

28

43

55

64

Condenser

22

28

43

55

64

MAXIMUM FLOW RATES (gpm)

Evaporator

74

97

148

188

220

Condenser

74

97

148

188

220