Potter PFC-4410RC User Manual

Page 55

Advertising
background image

55

PFC-4410RC • 5403550 • REV Q • 11/12

Program #20 Mode

1. Apply power to panel.
2. Move the program switch down.
3. Press the FUNCTION (bottom) button until the display reads “PASSWORD = 000”.
4. To enter a password, press the SELECT button until the proper number is displayed above the ^ symbol, then press the SET

button to move to the next digit. After entering the third number the display will change.
(All panels are shipped with a 000 password.)
5. Press the FUNCTION (bottom) button until the display reads “PROGRAM #0”.
6. Press the SELECT button until the display reads “PROGRAM #20”.
7. Press the SET button.
8. Press the SELECT button to change the pre-discharge time.
9. Press the SET button to enter the pre-discharge time displayed.
10. Press the SELECT button to change the abort mode. See page 10 for abort mode selections.
11. Press the SET button to enter the abort mode displayed.
12. The panel is completely programmed except for the custom banner and zone messages Move the program switch back up.

Description:

Dual Hazard, 2 detection zones cross-zoned to 1 release circuit and 2 other detection zones cross zoned to

another release circuit

Inputs:

1 supervisory zone, 4 detection zones, 1 abort circuit

Outputs:

2 general alarm, 2 release circuit

Operation:

Activation of either detection zones 1 and 2 will activate the alarm output #1

Activation of both detection circuits at the same time will start the pre-discharge timer for release circuit output

#2 as well as activate the alarm output #1

Activation of either detection zones 3 and 4 will activate the alarm output #3

Activation of both detection circuits at the same time will start the pre-discharge timer for release circuit output

#4 as well as activate the alarm output #3

When either zone 1 or 2 is in alarm, output 1 will operate

When both zones 1 and 2 are in alarm at the same time, the pre-discharge timer for output #2 will operate

When either zone 3 or 4 is in alarm, output 3 will operate

When both zones 3 and 4 are in alarm at the same time, the pre-discharge timer for output #4 will operate

PROGRAM #20

ZONES

SUPERVISORY 2

#1

#2

#3

#4

OUTPUTS

Supervisory

Detection

Detection

Detection

Detection

#1 ALARM INDICATING

X

X

#2 RELEASE

XX

XX

#3 ALARM INDICATING

X

X

#4 RELEASE

XX

XX

SUP 1 defaults to abort

XX = Cross-Zoned