Instructions to Re-Install the Burner (Refer to FIGURE 27)

1. Attach the Burner Assembly - Holding the venturi tube, slide the entire

burner assembly into position. Align the supports on the left side with the slots

in the burner shield; sliding the supports into the slots. On the right, re-attach

each burner body support to the secondary air shield.

2. Attach the Secondary Air Baffles - Re-attach the secondary air baffles as

marked. Baffles may be different sizes and each

must be attached in the

correct location.

3. Attach the Control Assembly - Carefully slide the control assembly

into position. Re-attach with the same screws. Check to be sure all wire

connections are secure.

4. Attach the Gas Train - Slide the gas train so that the orifice adapter is through

the bracket. Fasten the gas train to the bracket with the locking nut. Install the

gas orifice. Re-connect the wires to the gas valve.

5. Close the access panel.

6. Reconnect the gas supply at the union outside of the cabinet. Leak test the

connection with leak detecting solution.

7. Turn on the electric and the gas. Check for proper operation.

Re-Install the Burner

12.2.3 Burner Orifice

Burner orifice usually only needs to be replaced when installing a gas conversion

kit. If ordering a replacement orifice only, give BTUH content and specific gravity of

gas, as well as the model and serial number of the unit. When removing or replac-

ing the burner orifice, be careful not to damage the venturi tube and/or the bracket.

FIGURE 28 - Location of Controls

High Temperature

Limit Control

Gas Valve

Pressure

Switch

Venter

Vent Temperature

Limit Switch

Flame

Sensor

Ignitor

Fan

Motor

Control Panel Assembly

Door

Switch

Disconnect

Switch

Transformer

Fan Motor Capacitor

DSI Integrated Control

Module (Circuit Board)

Venter

Motor Capacitor

FIGURE 29 - DSI Integrated Control

Module (Circuit Board)

Only

replaceable

part is a Type

ATC or ATO

3 amp fuse

(Color Code

Violet),

P/N 201685

12.2.4. Ignition System

DSI Integrated Control Module (circuit board) - See FIGURE 29. The module

monitors the operation of the heater including ignition. The only replaceable com-

ponent is the 3 amp Type ATC or ATO fuse. If the fuse is blown, the problem is

most likely an external overload. Correct the problem and replace the fuse.