0 mechanical (cont'd), 4 discharge air (cont'd) – Reznor CAUA Unit Installation Manual User Manual

Page 28

Advertising
background image

Form I-CAUA, P/N 164771 R8, Page 28

Combustion Air

Knockout

Venter

Outlet

Electrical

Gas

6-3/8”

(162mm)

4-1/8”

(105mm)

2-3/8” (60mm)

A

B

Discharge

Airflow

Attach to the Duct Flange

Removable Access Panel in the

Ductwork - Minimum size is 6" x 10"

(152mm x 254mm). Panel must be

sealed.

FIGURE 22B -

Connecting Discharge

Ductwork

Heater

FIGURE 22A - Top View

showing Discharge Duct

Connection Dimensions

Top

View

Size

A

B

150,

200

36"

(914mm)

21"

(533mm)

250,

300

48"

(1219mm)

21"

(533mm)

350,

400

48"

(1219mm)

34"

(864mm)

TABLE 21 - Discharge Duct

Dimensions

Requirements and

Suggestions for

Connecting and

Installing Ducts

• Type of Ductwork - The type of duct installation to be used depends in part on the

type of construction of the building.

• Ductwork Material - Rectangular duct should be constructed of not lighter than

No. 26 U.S. gauge galvanized iron or No. 24 B & S gauge aluminum.

• Ductwork Structure - All duct sections 24 inches or wider, and over 48 inches

in length, should be cross broken on top and bottom and should have standing

seams or angle-iron braces. Joints should be S and drive strip, or locked.

• Through Masonry Walls - No warm air duct should come in contact with masonry

walls. Insulate around all air duct through masonry walls with not less than 1/2" (1"

is recommended) of insulation.

• Through Unheated Space - Insulate all exposed warm air ducts passing through

unheated space with at least 1/2" (1" recommended) of insulation.

• Duct Supports - Suspend all ducts securely from buildings members. Do not sup-

port ducts from unit duct connections.

• Duct Sizing - Proper sizing of the supply air ductwork is necessary to ensure a

satisfactory heating installation. The recognized authority for such information is

the Air Conditioning Contractors Association, 2800 Shirlington Road, Suite 300,

Arlington, VA 22206 (www.acca.org). A manual covering duct sizing in detail may

be purchased directly from them.

• Removable Panels - The ducts should have removable access panels on both

upstream and downstream sides of the furnace. These openings must be acces-

sible when the furnace is in service and should be a minimum of 6" x 10" in size so

6.0 Mechanical

(cont'd)

CAUTION: An

external duct

system static

pressure not within

the limits shown

on the rating

plate, or improper

motor pulley or

belt adjustment,

may overload the

motor. See Hazard

Levels, page 2.

6.4.1 Discharge Duct Connection (cont'd)

6.4 Discharge Air (cont'd)