10.5 Compressor

Maintenance

and

Replacement

(cont’d)

TABLE 9 (cont’d)- Replacement Scroll Compressors for R-410A

Refrigerant

10.0 Maintenance

and Service

(cont’d)

Step 2. Determine Cause of Initial Failure and Remove the Compressor

In order to prevent a second failure, the cause of the original failure must be

determined. Identify the cause and make the necessary repairs.

CAUTION

DO NOT LIFT compressor by copper tubing; damage will

occur. Compressor must remain upright. See Hazard Levels,

page 3.

WARNING

Wear eye protection, gloves, and protective clothing when

handling refrigerant, POE oil, and when brazing. See Hazard

Levels, page 3.

a) BEFORE REMOVING THE FAULTY COMPRESSOR, remove R-410A

refrigerant charge using proper recovery procedures. Call 1-800-441-

9450 for the name of the nearest *Dupont authorized distributor or

1-800-ASK-KLEA (IGI) for information on their refrigerant reclaim pro-

grams. This is a scroll compressor. Be sure to remove refrigerant from

both the high side and the low side.

WARNING

Do not release refrigerant to the atmosphere. When adding or

removing refrigerant, the qualified technician must comply

with all national, state/province, and local laws.

MASA

Model

Nominal

Tonnage

Voltage

Refrigerant

Circuit

Nominal

Tonnage

Compressor

Model*

Reznor

P/N

240

20

200-

230/3/60

A

7

ZP83K

216689

B

13

ZP154K

220260

480/3/60

A

7

ZP83K

216690

B

13

ZP154K

220261

575/3/60

A

7

ZP83K

216691

B

13

ZP154K

220262

*Model No. of replacement R410A scroll compressor must be identical to the one

removed including the "

E" (ZP39KxExxx) which indicates POE compressor oil.

b) Disconnect wires. Compressor wiring is connected either using a black

molded plastic plug or wire terminals. Either remove the plug from the

compressor or disconnect the wires.

c) Open access ports so that pressure does not build up in the system.

Before unbrazing, cut the suction and discharge tubing with a tubing

cutter.

WARNING

Have a fire extinguisher near. The compressor contains oil.

There is a risk of fire when unbrazing stubs. See Hazard

Levels, page 3.

Use a high temperature torch to disconnect the suction line and the dis-

charge line from the compressor.