3 typical wiring diagrams – Reznor RPB Unit Installation Manual User Manual

Page 25

Advertising
background image

Form I-RPB, P/N 131782 R12, Page 25

7.3 Typical Wiring Diagrams (Refer to the diagram supplied with the furnace for alternate

controls or optional equipment details.)

RELAY CONTACTS

TIME DELAY

& CAPACITOR

VENTER MOTOR

COMBUSTION

PRESSURE

SWITCH

L1

L2

L1

F

L2

8

8

8

10

10

12

1

2

2

RELAY CONTACTS

TIME DELAY

6

6

4

11

6

Y

Y

Y

W

BK

Y

Y

Y

Y

Y

W

12

BL

BL

R

R

R

BL

BK

BK

BK

BK

BK

W

7

7

7

BK

BR

21

H

TD

H

BR

BR

W

20

H

TD

H

BR

7

BK

BL

W

7

TIME DELAY

RELAY COIL

13 - 25

17

FAN TD

HEATER

BR

CR

17

BR

7

CONTACTOR COIL

BLOWER MOTOR

7 - 8 - 9

7

BR

TERMINAL BLOCK --

HEATER COMPARTMENT

TERMINAL BLOCK --

BLOWER COMPARTMENT

11, 12, L1, L2 & F

1, 2, 4, 6, 7, 8, 10,

12, L1 & L2

2, 6, 7, 8, 10,

RPB SERIES AH2 OR AH3-AG1-CL1 DWG. #B-274964 REV. #2 IJB

OPTIONAL FIELD WIRING

OPTIONAL FACTORY WIRING

FACTORY WIRING

FIELD WIRING

WHITE - W

PURPLE - PR

BLUE - BL

GREEN - G

YELLOW - Y

ORANGE - O

RED - R

BROWN - BR

BLACK - BK

WIRING CODE

TOTAL WIRE MINIMUM RECOMMENDED

LENGTH WIRE SIZE

150 FEET #18 GA.

250 FEET #16 GA.

350 FEET #14 GA.

FIELD WIRING

R

1/60 OR 3/60

LINE

GRD

G

R OR W

R OR BK

R

PROTECTED

BLOWER

MOTOR

INTERNALLY

CONTACTOR

BLOWER MOTOR

CONTACTS

L2

L3

L1

W

BK

BK

T1

T2

T3

OPERATING SEQUENCE
- SET THERMOSTAT AT LOWEST SETTING.

- TURN ON POWER AND MANUAL GAS VALVE TO UNIT.

- SET THERMOSTAT AT DESIRED SETTING.

- FIRING RATE IS CONTROLLED BY THE THERMOSTAT.

- BLOWER MOTOR OPERATES FROM FAN TIME DELAY.

40 VA. CONTROL

BK

BL

24V

LINE VOLT

BR

R

TRANSFORMER

Y

MAIN

PILOT

SET ANT. AT 1.0 AMPS

OPT. SINGLE STAGE

THERMOSTAT

R

W

UNIT AUTOMATIC

LIMIT CONTROL

LIMIT

AUTO RESET

REVERSE FLOW

- SET THERMOSTAT AT LOWEST TEMPERATURE FOR SHUTDOWN.

- BLOWER MOTOR REMAINS ON AS DETERMINED BY FAN TIME DELAY.

(SEE NOTES)

DISCONNECT SWITCH

REDUND

ANT

GAS V

AL

VE

AL

TERNA

TE

W

.R. OR R

OBER

TSHA

W

BL

P

BK

BR

M

AIN

PIL

O

T

M

C

PV

PIL

O

T

MV

PV-MV

M

AIN

REDUND

ANT

GAS V

AL

VE

HONE

YWELL

COM

NC

NO

CONTACTS

FAN TD

1

3

BK

ON 115/460V. UNITS THE CONTROL TRANSFORMER IS A SINGLE VOLTAGE PRIMARY.

- ON 208/230V. UNITS THE CONTROL TRANSFORMER HAS A DUAL VOLTAGE PRIMARY.

- USE #12 GA. WIRE FOR LINE AND MOTOR WIRING ON SINGLE PHASE UNIT.

- USE #14 GA. WIRE FOR LINE AND MOTOR WIRING ON THREE PHASE UNIT.

TO PREVENT VOLTAGE DROP BEYOND FIVE PERCENT OF SUPPLY LINE VOLTAGE.

- LINE AND BLOWER MOTOR BRANCH CIRCUIT WIRE SIZE SHOULD BE OF A SIZE

A TEMPERATURE RATING OF AT LEAST 105 DEGREES C., EXCEPT FOR SENSOR

MUST BE REPLACED, IT MUST BE REPLACED WITH WIRING MATERIAL HAVING

- CAUTION: IF ANY OF THE ORIGINAL WIRE AS SUPPLIED WITH THE APPLIANCE

- DOTTED WIRING AND THE FOLLOWING CONTROLS ARE SUPPLIED AND INSTALLED

- THE FOLLOWING CONTROLS ARE SUPPLIED AS OPTIONAL EQUIPMENT:

- THE FOLLOWING CONTROLS ARE SUPPLIED BY REZNOR FOR FIELD INSTALLATION:

FOR 115/460V. UNITS USE BLACK AND YELLOW LEADS.

FOR 208V. UNITS USE BLACK AND RED LEADS (CAP YELLOW).

FOR 230V. UNITS USE BLACK AND YELLOW LEADS (CAP RED).

THERMOSTAT

LEAD WIRE WHICH MUST BE 150 DEGREES C.

- USE #18 GA. WIRE FOR 24 VOLT CONTROL WIRING ON UNIT.

BY OTHERS: NONE

NONE

USE DUAL ELEMENTS TIME DELAY FUSES AND SIZE ACCORDING TO 1.25

TIMES THE MAXIMUM TOTAL INPUT AMPS.

- WHEN PROVIDING OR REPLACING FUSES IN THE FUSIBLE DISCONNECT SWITCH

- DISCONNECT SWITCH IS FIELD FURNISHED OR AVAILABLE FROM FACTORY AS AN OPTION.

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

FIRING SEQUENCE:

- ON A CALL FOR HEAT BY THE THERMOSTAT.

- THE VENTER MOTOR IS ENERGIZED AFTER A 15 SECOND (APPROX.)

TIME DELAY.

- VENTER FLOW SWITCH SWITCHES FROM N.C. TO N.O. CONTACTS ENERGIZING

FLAME ON EACH OPERATING CYCLE. THE SENSING PROBE PROVES THE

PRESENCE OF THE PILOT FLAME AND ENERGIZES THE SAFETY SWITCH

PORTION OF THE CONTROL. THE SWITCH ACTION DE-ENERGIZES THE

SPARK GAP AND ENERGIZES THE MAIN VALVE. THE MAIN GAS IGNITES

AND UNIT FIRES AT FULL RATE.

THE PILOT GAS VALVE AND SPARK GAP TO PRODUCE A PILOT

- IF THE FLAME IS EXTINGUISHED DURING MAIN BURNER OPERATION,

THE SAFETY SWITCH CLOSES THE MAIN VALVE AND RECYCLES THE

SPARK GAP.
ON UNITS EQUIPPED WITH LOCKOUT CONTROL, IF PILOT IS NOT

ESTABLISHED WITHIN 120 SEC. THE UNIT LOCKS OUT FOR ONE

HOUR, UNLESS IT IS RESET BY INTERRUPTING POWER TO
THE CONTROL CIRCUIT. (SEE LIGHTING INSTRUCTIONS)

M1(4)

M2(5)

M3(1)

M4(3)

BL

BK

IGNITION

CONTROLLER

PROBE

GND

SPARK

FLAME SENSING

MV/PV

MV

SENSE

TH

PV

Y

24V GND

BR

GND BURNER

G

BURNER

GROUND

NOTES:

FIGURE 27 - Typical Wiring Diagram Model RPB, Outdoor, Power-Vented Furnace with Standard

Single-Stage Gas Valve

Advertising