Is the vent terminal horizontal or vertical – Reznor SC Duct Furnace Unit Installation Manual User Manual

Page 13

Advertising
background image

Form I-SC, P/N 207696 R11, Page 13

When pipe diameters differ, depending on direction of airflow, join the pipes with either

a taper-type reducer or enlarger. Refer to illustrations in

FIGURE 9A and 9B for pipe

connection requirements at the concentric adapter box.
Do

NOT make actual connections until after reading the instructions and length require-

ments for installing the vent/combustion air kit.

The box connection requirements

are the same for both vertical and horizontal systems, but the length of the dou-

ble-wall pipe varies by installation.

Pipe Connections at the

Concentric Adapter Box

FIGURE 9A - Concentric

Adapter Box

Connections - 6" Pipe

Requires a 6 to 5 inch (152 to 127mm)

taper-type reducer a maximum of 6”

(152mm) from the concentric adapter box.

6” (152mm) diameter single-wall

inlet air pipe attaches to the heater

5” (127mm)

inside diameter

double-wall

vent pipe

Top View of Concentric Adapter

Box showing Pipe Connections

6” (152mm) diameter single-wall

or Category III vent pipe attaches

to the heater

8” (203mm)

diameter

single-wall

inlet air pipe

Model SC 100-400 - Pipe diameters and connections required at the

concentric adapter box when using 6” pipes between the furnace and

the box

• If using 6” diameter

pipes, Model SC 100-

400 always require a 6”

to 5” (152 to 127 mm)

reducer in the vent pipe.

Taper-type

Reducer

Airflow

• If using 7” diameter

pipes (allowed on Sizes

200-400), Models SC

200-400 always require a

7” to 5” (178 to 127 mm)

reducer in the vent pipe

and a 6” to 7” (152 to 178

mm) enlarger for attach-

ing the combustion air

pipe.

Requires a 7 to 5 inch (178 to 127mm)

taper-type reducer a maximum of 6”

(152mm) from the concentric adapter box.

7” (178mm) diameter single-wall

inlet air pipe attaches tot he heater

5” (127mm)

inside diameter

double-wall

vent pipe

Top View of Concentric Adapter

Box showing Pipe Connections

7” (178mm) diameter single-wall

or Category III vent pipe attaches

to the heater

8” (203mm)

diameter

single-wall

inlet air pipe

Models (H)SC 200-400 - Pipe diameters and connections required at the

concentric adapter box when using 7” pipes between the furnace and

the box

Requires a 6 to 7 inch (152 to 178mm)

taper-type enlarger at the concentric

adapter box.

Taper-type

Reducer

Airflow

Taper-type

Enlarger

Airflow

FIGURE 9B - Concentric Adapter Box Connections - 7" pipe

Horizontal,

Option CC6,

instructions

begin on page 14.

Vertical,

Option CC2,

instructions

begin on

page 17.

Follow the

instructions for

the Vent Terminal

being installed:

Is the Vent Terminal HORIZONTAL OR VERTICAL?