0 electrical supply and wiring, 1 general, 2 supply voltage and wiring – Reznor X Unit Installation Manual User Manual

Page 16: 3 thermostat and control wiring

Advertising
background image

Form I-X, P/N 150491 R10, Page 16

60°C. Be sure conduit from the disconnect switch will not interfere with the service

panels of the furnace.

If the heater has field-installed options that require electrical connections, consult the

instruction sheet and wiring diagram supplied in the option package.

Specific wiring diagrams that include standard and factory-installed options are included

with the heater.

Typical wiring diagrams of currently manufactured heaters are on

pages 17-18.

CAUTION: If any of

the original wire as

supplied with the

appliance must be

replaced, it must be

replaced with wiring

material having a

temperature rating

of at least 105°C,

except for limit

control, energy

cutoff, and sensor

lead wires which

must be 150°C.

Disconnect Switch

A disconnect switch is a required part of this installation. Switches are available, as

options or parts, or may be purchased locally. When ordered as an optional compo-

nent, the disconnect switch is shipped separately.

The disconnect switch may be fusible or non-fusible. When providing or replacing fuses

in a fusible disconnect switch, use dual element time delay fuses and size according to

1.25 times the maximum total input amps.

When installing, be careful that the conduit and switch housing are clear of furnace

panels and inspection plates. Allow at least four feet (1.2M) of service room between

the disconnect switch and removable panels.

7.3 Thermostat and

Control Wiring

A thermostat is not standard equipment but is an installation requirement. Use either

an optional thermostat available with the heater or a field-supplied thermostat. Install

according to the thermostat manufacturer's instructions.

A 24-volt thermostat must be used to actuate low voltage gas controls. If line voltage

from the thermostat to the unit is desired, consult the factory representative.

Wiring between the thermostat and the heater must be suitable for a temperature rise

of 60°C. Labeled thermostat leads are provided in the heater junction box for connec-

tion of thermostat wiring.

Thermostats should be located five feet (1.5M) above the floor on an inside wall, not

in the path of warm or cold air currents and not in corners where air may be pocketed.

Do NOT install a thermostat on cold air walls. For specific connection details, refer to

the instructions with the thermostat.

If more than one unit is cycled from one thermostat, separately activated relays must

be substituted at unit thermostat connections.

CAUTION: Make sure the thermostat has an adequate VA rating

for the total requirements. Add coil rating of all relays and match

thermostat rating. See Hazard Levels, page 2.

If the low voltage (24 volt) thermostat is equipped with a heat anticipator to level out

unit cycling for optimum temperature control, set the anticipator at full load control

AMPS.

24 Volt Controls - Maximum Amps

(24 volt Transformer has 20 VA capacity)

Single-Stage Valve .7A

Fan Control Heater .12A

Two-Stage Valve

.33A Time Delay Relay

Heater

.1A

Maxitrol System

.5A

Spark Ignition

.1A

Relay Coil

.12A

7.0 Electrical

Supply and

Wiring

7.1 General

All electrical wiring and connections, including electrical grounding MUST be made in

accordance with the National Electric Code ANSI/NFPA No. 70 (latest edition) or, in

Canada, the Canadian Electrical Code, Part I-C.S.A. Standard C22.1. In addition, the

installer should be aware of any local ordinances or gas company requirements that

might apply.

7.2 Supply Voltage

and Wiring

Check the rating plate on the heater for the supply voltage and current requirements.

Run a separate line voltage supply with fused disconnect switch directly from the main

electrical panel to the furnace, making connection to leads in the junction box. All exter-

nal wiring must be within approved conduit and have a minimum temperature rise of

Advertising