Form I-RDH/REH/RHH/RXH (12-14), P/N 215210 R14, Page 41

FIGURE 38 - Discharge

Air Sensor Holder,

P/N 115850, used in

Makeup Air Installations

Secure sensor in clip.

Position holder so that it

shields sensor from direct

airflow.

TABLE 26A - Digital Control

Signal Wire Gauge and Length

Maximum Sensor Wire Length for less than 1°F Signal Error

Wire Gauge

Maximum Sensor Wire Length (Digital Control)

AWG

Feet

Meters

14

800

244

16

500

152

18

310

94

20

200

61

22

124

38

bundled separately from the 24 VAC control wiring. The shield must be drained at

the unit and taped on the opposite end.

See

TABLE 26A for wire gauge and length requirements of digital control signal wiring.

(

NOTE: Sensor wire supplied

with the FX05 digital controller is

22AWG. There is no sensor wire

supplied with the FX06 controller;

it must be field supplied.)

connected to the main digital controller should be routed to the unit in one of the fol-

lowing manners:

In separate conduits, isolated from 24 VAC controls and line voltage power to the

unit,

OR

If the main controller sensor wires are to be run in the same conduit as the 24

VAC control wiring, the sensor wiring must be completed using shielded cable and

TABLE 26B - Sensor

Data for Johnson A99

Series Temperature

Sensors used in DG

and D12 Options -

Resistance VS

Temperature

°F

°C

Ohms

-40

-40

613

-31

-35

640

-22

-30

668

-13

-25

697

-4

-20

727

5

-15

758

14

-10

789

23

-5

822

32

-0

855

41

5

889

50

10

924

59

15

960

68

20

997

77

25

1035

86

30

1074

59

35

1113

104

40

1153

113

45

1195

122

50

1237

131

50

1279

140

60

1323

149

65

1368

158

70

1413

167

75

1459

176

80

1506

185

85

1554

194

90

1602

203

95

1652

212

100

1702

221

105

1753

230

110

1804

239

115

1856

248

120

1908

Instructions for Installing Discharge Air Sensor in the Ductwork

1. Installation requires the discharge air sensor holder including the box cover.

2. Determine a location in the ductwork to install the sensor. Select a location a

sufficient distance from the outlet to provide a good mixture of discharge air

temperature. If installing Options AG3 or AG60 with a capillary sensor, determine

the location based on the length of the capillary tubing.

If installing wiring to the sensor, select a location a sufficient distance from the

outlet to provide a good mixture of discharge air temperature. According to the

latest edition of AMCA Standard 201, in straight ducts, the air is typically well

mixed a minimum of five equivalent duct diameters from the discharge of the unit

with equivalent duct diameter defined as equal to the square root of 4AB/3.14. “A”

and “B” are the duct cross-sectional dimensions.

Example:

Supply ductwork cross-sectional dimension is

24" x 12" (610mm x 305mm).

5 x

4 x 12 x 24

3.14

= 96"

5 x

4 x 305 x 610

3.14

= 2435mm

Solution: Locate the sensor a minimum of 96" (2435mm)

from the outlet of the unit.

NOTE: If the length of the discharge duct is less than 8 ft (2.4M), a mixing vane is

recommended for mixing the discharge air.

Do not mount the sensor in the ductwork after a split in the supply as that will

cause loss of control in the duct that does not house the sensor.

3. The position of the sensor holder is important. The holder will extend 9-3/16”

(233mm) into the ductwork.
In horizontal ductwork, locate the sensor assembly in the top, middle of the duct

with the sensor probe extending vertically down into the center of the airstream.

In vertical ductwork, locate the sensor assembly in the middle of the side of the

duct that corresponds with the top middle of the discharge outlet.
Turn the holder so that the element will be shielded from direct airflow and will

sense the air temperature as it flows through the holes in the holder.
At the selected location in the ductwork, mark the diamond-shaped hole required

for the sensor holder. Cut the hole no larger than required, approximately 1” x 1”

(25mm x 25mm).

4. The procedure for installing the sensor and attaching the holder depends on

whether the sensor is a capillary or an electrical sensor. Follow the instructions

that apply.

Capillary Sensor (Option AG3 and AG60) - Locate the sensor capillary and run

it out through the hole in the discharge panel of the heater. Determine where the

sensor capillary should enter the box and remove the knockout. Put the capillary