Reznor UDBP High altitude installation instructions User Manual

Options dj20 & dj21 application, Kit components, Standard power vent unit heaters

Advertising
background image

Form I-UD&APD Series-HA (11-14), Page 1

APPLIES TO:

Standard Power Vent Unit Heaters:

Models UDAP, UDBP and ADP

Separated Combustion Unit Heaters:

Models UDAS and UDBS

FORM I-UD&APD Series-HA (11-14)

Obsoletes Installation Form RZ-NA- I-UD-HA

High Altitude Kits for Elevations above 6000Ft / 1830M

Options DJ20 & DJ21

Application

If a Standard Power Vent or Separated Combustion Unit Heater is being installed above 2,000 ft

(610 M), the input rate must be derated. This is done by adjusting the valve outlet pressure as

explained in the heater installation manual. In addition, if the heater is being installed at an altitude

above 6,000 ft (1,830 M), the pressure switch must be changed.
The high altitude pressure switch ordered as Option DJ20 or DJ21, High Altitude Kit, varies by

Model, Size and type of application. Option DJ20 or DJ21 is

REQUIRED above 6,000 ft (1,830 M)

Be sure your kit matches your installation.

Option DJ20

Installed as

a Std. Power

Vented Fan

Type Unit

Heater

Std Power Vent Unit

Heater

30

45

60

75

100

125

150

175

200

225

250

300

350

400

Pkg P/N

197117

197118

197117

201162

201163

High Altitude Switch P/N

197031

197032

197031

201160

201161

Negative Pressure

OFF Setpoint “w.c.”

0.35

0.45

0.35

1.00

1.30

Label Color

Purple

Pink

Purple

Brown

White

Option DJ21

Installed as

a Std. Power

Vented Fan

Type Unit

Heater with

Option AV6

for Common

Venting

Std Power Vent Unit

Heater w/ Opt AV6

30

45

60

75

100

Pkg P/N

197119 197118

197120

197121

High Altitude Switch P/N

197029 197032

196362

196388

Negative Pressure

OFF Setpoint “w.c.”

0.60

0.45

0.55

0.50

Label Color

Lt Blue

Pink

White

Orange

Option DJ20

Installed as

a Separated

Combustion

Fan Type Unit

Heater

Separated Combus-

tion Unit Heater

30

45

60

75

100

125

150 175

200

225

250 300

350

400

Pkg P/N

197119

197121 197205

197117

201162

201163

High Altitude Switch P/N

197029

196388 197030

197031

201160

201161

Negative Pressure

OFF Setpoint “w.c.”

0.60

0.50

0.40

0.35

1.00

1.30

Label Color

Lt Blue

Orange

Green

Purple

Brown

White

Option DJ20

Installed

as a Std.

Power Vented

Blower Type

Unit Heater

Std Power Vent Unit

Heater

30

45

60

75

100

125

150

175 200 225 250 300

350

400

Pkg P/N

197117

197118

197117

201162

201163

201162

High Altitude Switch P/N

197031

197032

197031

201160

201161

201160

Negative Pressure

OFF Setpoint “w.c.”

0.35

0.45

0.35

1.00

1.30

1.00

Label Color

Purple

Pink

Purple

Brown

White

Brown

Kit Components

Option DJ20

Installed as

a Separated

Combustion

Blower Type

Unit Heater

Separated Combus-

tion Unit Heater

30

45

60

75

100

125

150

175 200 225 250 300

350

400

Pkg P/N

197117 197118 202103 197118 197117 197205

197118

201162

201163

201162

High Altitude Switch P/N

197031 197032 196362 197203 197031 197030

197031

201160

201161

201160

Negative Pressure

OFF Setpoint “w.c.”

0.35

0.45

0.55

0.45

0.35

0.40

0.35

1.00

1.30

1.00

Label Color

Purple

Pink

White

Pink

Purple

Green

Purple

Brown

White

Brown