Reznor VR Option - Installation - Multiple Heater Control (Options CL31 and CL32) User Manual

Description/ application, Kit components by model

Advertising
background image

Form I-OPT-MH, P/N 102247 R7, Page 1

Applies to:

Reznor

®

Models LDAP, UDAP, UDAS,

UDBP, UDBS, UEAS, F, B, VR

Description/

Application

These options are designed to permit the control of up to six heaters (one "Primary" heater

and one to five "Secondary" units; see note for LDAP limitations) with one single-stage ther-

mostat or with a time clock and single or multiple single-stage thermostats. For maximum

safety, the multiple control is done in the low voltage circuit. (Interruption of the supply volt-

age is not recommended.) Wiring lengths may not exceed those shown in the table on page

8.

DO NOT use these multiple heater control options with a two-stage gas valve or a

two-stage thermostat.

Kit Components

by Model

Check the components

against the list for the

model being installed.

Model LDAP

Model UDAP

Model UDAS

Model UDBP

Model UDBS

Model UEAS

Model F

Model B

Model VR

Installation of Multiple Heater Control, Options CL31 and CL32

Form I-OPT-MH (Version D)

Obsoletes Form I-OPT-MH (Version C)

Application

by Voltage

& Model

Model LDAP

Models UDAP,

UDAS, UDBP,

UDBS, and UEAS**

Models F, B, and VR

Application

by Voltage

& Model

115/1

N/A

CL31 for both the

Primary and 1st

Secondary Heater

plus a CL32 each

for the 2nd, 3rd, 4th,

and 5th Secondary

Heaters.

CL31 for both the Primary and 1st

Secondary plus a CL32 each for 2nd,

3rd, 4th, and 5th Secondary Heaters.

115/1

208/1

CL31 for both the Primary

and 1st Secondary Heater

plus a CL32 each for the

2nd, 3rd, 4th, and 5th

Secondary Heaters. *

CL32 for the Primary Heater plus

CL32 each for 1st, 2nd, 3rd, 4th, and

5th Secondary Heaters.

208/1

230/1

230/1

208/3

N/A

208/3

230/3

N/A

230/3

460/3

N/A

460/3

575/3

N/A

CL31 for both the Primary and 1st

Secondary plus a CL32 each for 2nd,

3rd, 4th, and 5th Secondary Heaters.

575/3

* Model LDAP 400 can have five secondary heaters; Model LDAP 800 can have a maximum of three secondary

heaters; and Model LDAP 1200 can have a maximum of two secondary heaters.

** Model UEAS is 115 volt only.

Kits for Model LDAP

Option CL31 for LDAP -

Pkg P/N 208366 for Primary and One Secondary Unit

Qty

P/N

Description

2

208365 Relay Assemblies each consisting of one P/N 18549 relay, with attached

42" red wire, 42" white wire, 6" blue wire, and 6" brown wire -- all with

terminals.

2

208185 Wiring Diagram Label

Option CL32 for LDAP -

Pkg P/N 208367 for each Additional Secondary Unit

Qty

P/N

Description

1

208365 Relay Assemblies each consisting of one P/N 18549 relay, with attached

42" red wire, 42" white wire, 6" blue wire, and 6" brown wire -- all with

terminals.

1

208185 Wiring Diagram Label

Kits for Models UDAP, UDAS, UDBP, UDBS, UEAS

Opt CL31 for UDAP/UDAS/UEAS -

Pkg P/N 197155 for Primary & One Secondary Heater

Qty

P/N

Description

1

194808 Transformer 40VA

2

197157 Relay Assemblies each consisting of one P/N 18549 relay, wired and

mounted on a specially designed bracket.

2

195249 Self-drilling screw for attaching relay bracket

2

16228 Cable Clamp 3/16"

2

197164 Wiring Diagram Label

1

197160 Wiring Harness Assembly (brown wires)

Advertising