Form I-UDAS/UDBS-ASC, P/N 209344R6, Page 1

Installation of Compact, Aesthetic

Concentric Vent/Combustion Air,

Horizontal Vent Kit, Option CC14

Form I-UDAS/UDBS-ASC (Version A.1)

Obsoletes Form I-UDAS/UDBS-ASC (Version A)

Applies to: Models UDAS and UDBS,

Sizes 30, 45, 60, and 75

®

Application

Components

This option is designed for horizontal venting of Models UDAS and UDBS Sizes 30, 45, 60,

and 75. When vented horizontally, these models are Category III appliances. Option CC14

is a separated-combustion vent terminal/combustion air kit.
When an existing appliance is removed or replaced in a venting system, the venting sys-

tem may not be properly sized to vent the attached appliances. An improperly sized venting

system may result in the formation of condensate, leakage, and/or spillage.
Model UDAS 30, 45, 60, and 75 are certified for both residential and commercial/industrial

installations. Utility heaters certified for “residential use” are intended for heating of non-liv-

ing spaces that are attached to, or part of, a structure that contains space for family living

quarters. They are not intended to be the primary source of heat in residential applications

or to be used in sleeping quarters.
Model UDBS 30, 45, 60, and 75, are certified only for commercial/industrial installations.
These instructions apply to both residential and commercial/industrial installations.

P/N

Qty Description

208994

1

Assembled Vent/Combustion Air Terminal (See

FIGURE 2.)

209320

1

Concentric Adapter Box (See

FIGURE 4)

209337

2

Mounting Brackets

195638

6

Sheetmetal Screws #8-18 X 3/8

209338

1

Sealing Gasket

53335

1

Clear Sealant, #732, 3 oz tube

Option CC14, Pkg P/N 209343, includes:

Installation

Instructions

1. Select a location on the outside wall that is in compliance with the vent length, wall

thickness, and clearance requirements in

FIGURE 1 and TABLE 1 and TABLE 2.

2. Prepare the wall. At the selected location, cut a 4-1/2 inch (114mm) diameter

clearance hole in the wall.

IMPORTANT: Venting

must comply with any

additional requirements

in Form I-UD-V-SC

(supplied with the

heater).

WARNING: Installation should be done by a qualified service

agency in accordance with these instructions and in compliance

with all codes and requirements of authorities having jurisdiction.

Failure to follow instructions could result in death, serious injury,

and/or property damage. The qualified agency performing this

work assumes responsibility for this installation.

NOTE: Siding and trim

block are not included

in the vent kit. See

component list below.

Outside view of an

Option CC14 Vent

Terminal Installation

WARNING: Use this option only on the specified heater models and sizes. Any other

use could result in an unsafe condition that could cause damage to the heater,

property damage, personal injury and/or death.