Mfg No. 160202, Page 1

APPLIES TO:

Models RGBL,RPBL,SSCBL,PGBL;

Models ADF/ADFH 700/1200; Model RBL

OPTIONS AS3, AS4, AS5, AND AS8
EVAPORATIVE COOLING MODULE

INSTALLATION/OPERATION/MAINTENANCE

FORM RZ/NA I-OPT-EC

OBSOLETES FORM 400EC

®

NOTE:

After installation, keep this

booklet with the makeup air system

installation/operation manual.

1. Description/

Application

2. Dimensions

The optional evaporative cooling module for packaged indirect-fired system Model
Series RGBL, RPBL, SSCBL, PGBL, blower cabinet Model RBL, and direct-fired
makeup air Models ADF/ADFH 700/1200 is factory assembled but requires field
installation. Evaporative cooling module Option AS3 includes 6” rigid cellulose
media; Option AS4 includes 12" rigid cellulose media; Option AS5 includes 6"
rigid glass fiber media; and Option AS8 includes 12" rigid glass fiber media. The
base parts for supporting the evaporative cooling module and the transition duct for
connecting it to the unit are shipped with the module for field assembly and instal-
lation. If optional moisture elimination pads, a drain and fill kit, and/or a water
hammer arrestor are to be included in the installation, they also require field instal-
lation.
Indoor Installation Note:

The evaporative cooling module cannot be suspended;

it must be placed on a platform. If the installation is not conducive to providing a
platform for the optional evaporative cooling module to attach directly to the cabi-
net, install a compatible Reznor

®

Model REC evaporative cooling module which

also must be mounted but requires a field-fabricated transition duct and can be
located further away. All evaporative cooling modules require outside air.

3. Installation

Preparation
Check List:

o Make certain the installation complies with all local, utility and federal build-

ing and safety codes and regulations.

o Check module for shipping damage. If damage is found, document the damage

with the transporting agency and immediately contact your Reznor Distributor.

56-5/8”

(1438)

12

(305)

AIR

FLOW

58-3/4” (1492mm)

1” (25mm)

47-3/4”

(1213)

1” (25mm)

Opening Size

56-3/4 (1441) x 48 (1219)

2(51)

6 (152)

47-3/4 (1213)

5-1/2 (140)

Adjustable Legs

16 (406) maximum

9 (229) minimum

6 (152)

21-1/2

(546)

24

(610)

Drain/Overflow Connection

(centerline)

Water Connection

(1/4” tubing)

Adjustable

21-9/16 (548)

maximum

14-9/16 (370)

minimum

29-3/4

(756)

2(51)

5-1/32

(128

)

3 (76)

Contr

ol Pump

Access P

anel

Control

Side

View

Inlet View

54-1/16 (1373)

Transition Duct Opening

for Reznor Model Series

RGBL, RPBL, SSCBL, and

PGBL; Blower Model RBL;

and Model ADF/ADFH

Sizes 700 and 1200.

Water

Connection

(Control

Side)

Outlet View

9-1/2

(241)

2(51)

Drain/Overflow

Connections

Transition Duct Hardware Package
#10x1/2” Screws

(58) 11813

1/4 - 20 Hex Head Bolts (10) 16246
1/4 - 20 Nuts

(10)16050

o Check fabricated parts in the duct kit

package against parts list shown in
FIGURE 2

, page 3. The package

also includes the hardware listed
here.