Reznor B Option - Installation - Relay & Thermostats Installation User Manual

Applies to: models f, fe, b, and be, Description

Advertising
background image

Form RZ-NA-I-F/B-R, Mfg #98149 Rev 4, Page 1

HAZARD INTENSITY LEVELS

1. DANGER: Failure to comply will result in severe personal

injury or death and/or property damage.

2. WARNING: Failure to comply could result in severe per-

sonal injury or death and/or property damage.

3. CAUTION: Failure to comply could result in minor per-

sonal injury and/or property damage.

INSTALLATION FORM RZ-NA -I-F/B-R

Obsoletes Form 434/436-R (Version A)

APPLIES TO:

Models F, FE, B, and BE

OPTION CL21 Relay

OPTIONS CL17, CL18,

CL19 & CL20 Thermostats

Option CL21 Relay

Option CL21 relay must be installed for automatic fan or blower con-

trol through the thermostat. Option CL21 includes the relay and the

required electrical connections for installation; it does not include the

thermostat.
Option CL21 Relay, Option Package (P/N 98497) includes:

WARNING: Improper installation, adjustment,

alteration, service, or maintenance can cause

property damage, injury or death. Read the

installation, operation, and maintenance instructions

thoroughly before installing or servicing this

equipment.

Hold the relay in line with the holes and attach it with the two

plastic fasteners.

INSTALLATION NOTE: If the relay is not installed in the correct

location, the relay wiring length will be incorrect.

4. Install the 4-Screw Terminal Strip -- If the heater is equipped

with a two-screw terminal strip, it must be replaced with the four-

screw terminal strip in the option package. Mark all wires and

disconnect them from the terminal strip.

INSTALLATION AND WIRING
INSTRUCTIONS FOR OPTIONAL RELAY

Installation should be done by a qualified agency in accordance with the

instructions on this sheet and in compliance with all codes and require-

ments of authorities having jurisdiction.

1. If the heater is installed, turn off the gas and the electric

power.

2. Remove the outer panel on the left side of the heater (left when

facing the back of the heater), exposing the inner side panel and

wiring.

3. Attach the Relay -- On the vertical partition of the inner side panel,

locate the pre-punched holes for mounting the relay (See Figure 1).

Figure 1 - Relay Installation

DESCRIPTION

Plastic

Dart

Fasteners

Vertical

Partition

Inner Side Panel

Relay Mounting Locaiton

Relay

Cable

Holder

(NOTE: Some heaters

were manufactured with

a horizontal metal

partition in place of the

cable holder shown in

the illustration. If your

heater has a metal

partition, be sure to

install the bushing in the

hole to protect the

wires.)

Option Description

Option Pkg P/N

CL21 Relay

98497

CL17 One-Stage Thermostat with Relay

98474

CL18 Two-Stage Thermostat with Relay

98494

CL19 Air Recirculation Kit

98495

CL20 Air Recirculation Kit with Summer

Fan/Blower Switch

98496

Item Qty

P/N

Description

1

1

98118 RBM Relay

2

2

101798 Plastic Dart Fastener

3

1

96511 4-Screw Terminal Strip Connector

4

2

97023 Black Wire Assembly, 14 gauge x 8" long

5

1

97478 Brown Wire Assembly, 18 gauge x 18" long

6

1

98125 Purple Wire Assembly, 18 gauge x 18" long

7

1

98117 Open/Closed Bushing (See NOTE, Figure 1)

Thermostat Options

In addition to the thermostat, Thermostat Options CL17, 18, 19 and 20

include the following components:

Option

CL17

CL18

CL19

CL20

Same Components by Item No.
as in Option CL21 above

Items 1-

7 (all)

Items 1-

6

Items 1-

7 (all)

Items 1-

7 (all)

Additional Component
Terminal Jumper, P/N 123942

N/A

1

N/A

1

Install the thermostat according to the manufacturer's instructions. Make

wiring connections according to the wiring diagram illustrations in Fig-

ure 4 on the reverse side of this sheet. Follow the instructions below

for installing the relay.

®